Installation & Operation Manual Proven Quality since 1892
ECON actuator Fig. 7907, type ELA80
–
3000
Rev.19
–
April 2, 2021
24
4.9.2 PCU-A
–
Proportional Control Unit Alternating Current
PCU-A (1P and 3P) High performance Controller, using a 10 bit A/D converter and 8 bit
microprocessor technology.
PCU-A Features
Model
PCU-A (1 Phase and 3 Phase)
Power
85 ~ 260 VAC Free Voltage ± 10%, 50/60Hz, Max. 4 VA
Input Signal
4~20mA DC, 1~5V DC, 2~10V DC, 0~5V DC, 0~10V DC
Input Impedance
250
Ω
Output Signal
4~20mA DC, 1~5V DC, 2~10V DC, 0~5V DC, 0~10V DC
Output Impedance
250
Ω
Max
Output Contact
1 (Fault monitor)
Deadtime Adjustment
0.05~7.5 seconds
Deadband Adjustment
0.0625~1mA (0. step no. x 0.0625mA, 15 steps total)
Ambient Temperature
-10°C (14°F)
up
to +70°C (158°F)
Ambient Humidity
90% RH Max (non-condensation)
The factory settings of the PCU card are normally set according to the customer requirements at the
time of order. However, we strongly recommend that input power, signal input selection and DIP switches
are to be verified prior to the actuator start up.
Settings the PCU functions are shown in paragraph 4.9.4 and 4.9.5.
PCU-A 1P
PCU-A 3P