23
EN
420010334906
Max Gas 350 - 500 PR-MD
-
1
,
0
0
,
0
1
,
0
2
,
0
3
,
0
4
,
0
5
,
0
6
,
0
7
,
0
8
,
0
50
100
150
200
250
300
350
400
450
500
550
600
pressione
ca
m
era
di
co
m
b
u
stione
m
bar
k
W
11
,
5
12
12
,
5
13
14
15
16
1
2
3
5
4
posizione
testa
pressione
gas
in
testa
m
bar
EXAMPLE OF PRE-CALIBRATION MAX GAS 500
Warning:
the pre-calibration values have been
determined on EN676 test combustion cham-
bers in ideal conditions, and are useful for the
first switch-on but must be checked and correc-
ted with calibration for the individual system.
Example in figure
:
Power required by the generator: 380 kW.
Pressure envisaged in combustion chamber: 3.5
mbar. Combustion head chamber: 2.5 (between
2 and 3). Gas pressure in head: 13 mbar.
ADJUSTING THE AIR PRESSURE SWITCH
The air pressure switch must be adjusted so that an insufficient air flow does not allow
the CO value to exceed 1% in volume. After having adjusted the gas flow and obtained
optimum combustion (CO
2
= 9.5 to 9.8% and a CO value of less than 75 ppm), the air
pressure switch must be adjusted. Remove the cover with the burner operating, cover
the air intake progressively with a piece of cardboard to obtain a value of CO
2
= 10.8
(G20-G25)> 13 (G30-G31) and a CO value of less than 5,000 ppm. Adjust the air
pressure switch until the burner shuts down. Remove the cardboard from the air intake
and start up the burner again. Replace the cover.
ADJUSTING THE GAS PRESSURE SWITCH
Adjust the pressure switch to 50% of the feeding pressure of the gas used.
0,4
0,6
0,9
3,0
1,5
2,1
1
,8
2,4
2,7
1,
2
A
B
2,5
5
10
15
50
25
35
3
0
40
45
20
C
D
Gas pressure in head
Head position
Pressure in comb. chamber
With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner is run-
ning, and is properly adjusted, the value read must be steady and never be smaller than 3 µA (LME 22) .
FLAME DETECTION SYSTEM CHECK
Siemens
LME
11
/LME
21
-
22
min. 3 μA
1
Summary of Contents for MAX GAS 350 PR-MD
Page 12: ...12 420010334906 Max Gas 350 500 PR MD IT 7 7 7 8 9 10 11 12 SMONTAGGIO TESTA 1 2 3 4 5 6 ...
Page 25: ...25 EN 420010334906 Max Gas 350 500 PR MD 7 7 7 8 9 10 11 12 REMOVING FIRING HEAD 1 2 3 4 5 6 ...
Page 67: ...67 420010334906 Max Gas 350 500 PR MD IT EN FR ES RU ...
Page 68: ...68 420010334906 Max Gas 350 500 PR MD IT EN FR ES RU ...