pag.10

LB1317  

Maior P 45/60/80/120 PR 

SETTING PARAMETERS

When the burner is ignited all displays of the regulator light up.  The set point display will blink for about 10 seconds.  The value
in the upper field of the display (red) indicates the actual value.  The value in the lower field of the display (green) indicates the set
point currently programmed. 

CHANGING THE SET POINT

To change the set point, proceed as follows: 

--

--

Press the 

PGM

PGM

button to access the user level. SP1* will appear in the lower display

--

--

  

  

Change the value of set point SP1 using the t and s keys.

.

--

--

  

  

After a 2 second delay the value set is stored automatically –

To return to normal display press 

EXIT

EXIT

**

The value of SP1 depends on the value set previously in configuration level 

C111

.

SETTING PID PARAMETERS

PID parameters are factory set to standard mean values.  The operation of the regulator can be self-adapted to suit the system by
activating the “tunE” function. The regulator will set the PID parameters automatically.  To activate the “tunE” function proceed
as follows:  

--

--

  

  

With the burner in operation, press  

PGM 

PGM 

--

--

  

  

the caption “tunE*” will blink in the display. – When “tunE”

stops blinking, the self-adaptation routine has been completed. 

--

--

  

  

Confirm the computed parameters by pressing the 

key for 2

seconds. 

**  

The “tunE” function cannot be activated in Manual mode, or when the burner is off. 

The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-
ve action time dt and the integral action time rt. 

To change parameters Pb1, dt and rt, proceeds as follows: 

--

--

  

  

Press the 

PGM

PGM

button to access the parameters level. 

--

--

  

  

To move from

one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

Pb1

is displayed, the value can be increased or decreased using the s and t keys.  

--

--

Confirm the changed parameters by pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored auto-

matically. 

--

--

  

  

Press 

PGM

PGM

to access the next parameter. 

--

--

  

  

When dt is displayed, repeat the procedure described above. 

--

--

  

  

Press PGM

to access the next parameter. 

--

--

  

  

When rt is displayed, repeat the procedure above. 

--

--

  

  

To return to normal display press  

EXIT

EXIT

DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power.  HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off.  To set HYS1 and HYS3 proceed as follows: --

--

  

  

Press

the 

PGM

PGM

key to access the parameters level. 

--

--

  

  

To move from one parameter to the next, press 

PGM

PGM

--

--

  

  

When 

HYS1

is displayed

(burner ignition differential-stage II), increase or decrease the value using the 

and 

keys. 

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically. 

--

--

  

  

Press 

PGM

PGM

to access the

next parameter. 

--

--

  

  

When 

HYS2

is displayed (burner shutoff differential-stage II), repeat the procedure described above. 

--

--

  

  

Press

PGM

PGM

to access the next parameter. 

--

--

  

  

When 

HYS3

is displayed (upper shutoff differential) repeat the procedure described above. 

--

--

  

  

To return to normal display press 

EXIT

EXIT

MANUAL/AUTOMATIC MODE

To access “MANUAL” mode, press and hold 

EXIT

EXIT

for at least 5 seconds.  Manual mode can only be selected when the burner is

in operation.  It is deactivated automatically when the burner shuts off.  When the LED above the hand symbol is alight, the regu-
lator is in manual mode and the position of the servocontrol can be changed using the 

and 

keys. The LEDS on the front of

the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active.  Pressing the 

key the servocon-

trol OPENS. Pressing the 

key the servocontrol CLOSES.  To select automatic mode press and hold 

EXIT

EXIT

for at least 5 seconds.

The LED above the hand symbol goes out and the regulator reverts to automatic. 

CLIMATIC COMPENSATION

The RWF 40 regulator can be set with the set point interlocked to the external probe.  To select this operating mode, proceed as
follows:  

--

--

  

  

Connect the required probe as in the wiring diagram.  

--

--

  

  

Change the regulator settings.  When using an external probe

the regulator must be set as follows:  

--

--

  

  

Press the 

PGM

PGM

key to access the configuration level.  When the caption 

C111

(XXXX) is

displayed, use the 

key to access the second figure (XXXX).  Use the 

key to select the type of probe (XX3X).  

--

--

  

  

Confirm the

change of  parameters by pressing 

PGM

PGM

.  If this is not done within 2 seconds, the value is stored automatically  

--

--

  

  

Press 

PGM

PGM

to

access the configuration level.  When the display reads 

C112

(XXXX), use the 

key to access the second figure (XXXX).  Press

the 

key to set the type of probe (XX3X).  

--

--

  

  

Confirm the changed parameters by pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given

within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

. To establish the heating curve, proceed as follows: 

--

--

  

  

Press 

PGM

PGM

to access the parameters level.  

--

--

  

  

Press 

PGM

PGM

to move from one parameter to the next.  

--

--

  

  

When the letter H is

displayed (heating curve gradient), increase or decrease the value using the 

and 

keys.  

--

--

  

  

Confirm the changed parameters by

pressing 

PGM

PGM

.  

--

--

  

  

If confirmation is not given within 2 seconds the value will be stored automatically.  

--

--

  

  

To return to normal display press 

EXIT

EXIT

.

Summary of Contents for Maior P120 MD

Page 1: ...LB 1317 02 07 2004 MAIOR P 45 PR MD MAIOR P 60 PR MD MAIOR P 80 PR MD MAIOR P120 PR MD 230 400 V 50Hz techniques for energy saving OIL BURNERS...

Page 2: ...Thermal power max kcal h 459 000 600 000 800 000 1 200 000 kW 532 710 949 1423 Thermal power min kcal h 255 000 350 000 400 000 700 000 kW 296 415 474 830 Max flow rate light oil kg h 45 60 80 120 Mi...

Page 3: ...CHEITE CORDO OVERALL DIMENSIONS BURNER INSTALLATION 1 BURNER 2 NUT 3 WASHER 4 GASKET 5 BOLT 6 BOILER 7 GASKET MODELS A B C D D1 E F G I L M MAIOR P 45 PR MD 590 330 260 225 385 555 160 385 190 190 M10...

Page 4: ...18 10 5 2 45 38 33 20 10 4 AS 67 AN 77 m AJ 6 m Two pipe lift system Two pipe siphon feed system Pipe length Pipe length NOZZLE OUTPUT TYPE MONARCH F80 BPS NOZZLE PUMP PRESSURE RETURN PRESSURE BAR 20...

Page 5: ...rting the burner bleed the air in the pump through the gauge port Fill the piping with light oil to facilitate the pump priming Start the burner and check the pump feeding pressure In case the pump pr...

Page 6: ...response switches BURNER START UP AND ADJUSTMENT OIL DELIVERY ADJUSTMENT The diagram illustrates the fuel feeding system of these types of burners which incorporates a by pass nozzle with oil flow re...

Page 7: ...the air damper until you reach the correct air flow as established by analyzing the combustion process tighten the Allen screw in place once again MAXIMUM CAPACITY ADJUSTMENT OF THE BURNER Position t...

Page 8: ...or Description I Limit switch for air damper High Flame position adjustment II Limit switch for ignition flame Min power position adjustment III Limit switch for air damper Low Flame position adjustme...

Page 9: ...E 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value and...

Page 10: ...access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Confirm...

Page 11: ...Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P active...

Page 12: ...ulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value is n...

Page 13: ...nto safety condition Control box is defective Ignition transformer is defective Electrodes are dirty Electrodes are defective Electrodes are in wrong position Nozzle is clogged Nozzle is too worn Filt...

Page 14: ...probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112 00...

Page 15: ...DELLA DITTA ECOFLAM S p A DESCRIZIONE MODIFICA DISEGNATO CONTROLLATO DATA FIRMA DATA FIRMA DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO...

Page 16: ...STC SAL KMV HLF HLB KT FMV TV MV FU Z Q THERMOSTAT GRANDE PETIRE ALLURE COMMUTATORE MANUALE AUTOMATICO INTERRUPTEUR MANUEL AUTOMATIQUE CONMUTADOR MANUAL AUTOMATICO TERMOSTATO DI ALTA BASSA FIAMMA SWI...

Page 17: ...0 8 9 11 13 A B C 3 M LINE LOAD PAGINA DI 00 01 02 03 04 05 06 07 08 09 A 00 01 02 03 04 05 06 07 08 09 B C D E A B C D E S p A SOST DA IND MOD SOST IL PROPRIETA RISERVATA DELLA DITTA ECOFLAM S p A DE...

Page 18: ...OR MOTOR VENTILATOR YVg STS STC SAL KMV HLF HLB KT FMV TV MV FU Z Q THERMOSTAT GRANDE PETIRE ALLURE COMMUTATORE MANUALE AUTOMATICO INTERRUPTEUR MANUEL AUTOMATIQUE CONMUTADOR MANUAL AUTOMATICO TERMOSTA...

Page 19: ...80 120 PR MD 38 8 10 13 28 7 21 39 9 36 14 15 12 11 23 25 24 18 22 17 16 26 27 FI N D ER FI N D ER 1 5 4 6 41 29 30 42 43 44 45 90 90 60 30 0 3 0 6 0 43 44 46 19 32 20 34 33 35 37 31 40 47 3 2 0 AUTO...

Page 20: ...M T105 1 T105 1 22 MANUAL AUTOMATIC SELECTOR R1020 5 R1020 5 23 MAIN SWITCH cod 40100I1509 R1020 R1020 24 FUSE HOLDER Fusit FH B528 E802 2 E802 2 25 LAMP EL N SC4 Elettrospring E1510 E1510 26 RELAY BA...

Page 21: ...105 1 T105 1 22 MANUAL AUTOMATIC SELECTOR R1020 5 R1020 5 23 MAIN SWITCH cod 40100I1509 R1020 R1020 24 FUSE HOLDER Fusit FH B528 E802 2 E802 2 25 LAMP EL N SC4 Elettrospring E1510 E1510 26 RELAY BASE...

Page 22: ...cessarie o utili senza pregiudicarne le caratteristiche principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ec...

Reviews: