FAULT FINDING
IMPORTANT
• Any required parts should be purchased from Mitsubishi Electric parts.
• Disconnect the electrical supply before removing any electrical equipment covers.
• NEVER bypass any thermal controls or operate system without the necessary safety valves.
• Water contained in the Air Source Heat Pump pre-plumbed cylinder may be very hot, especially following a thermal control
failure. Caution must be taken when drawing water from the unit.
The fault finding table (above) will enable operational faults to be identified and their possible causes rectified. Any work carried
out on this unvented water heater and its associated controls MUST be carried out by a competent installer for unvented
water heating systems. In case of doubt contact Technical Support (see contact details on back page).
WARNING
DO NOT TAMPER WITH ANY OF THE SAFETY VALVES OR CONTROLS SUPPLIED WITH THE PRE-PLUMBED CYLINDER
AS THIS WILL INVALIDATE ANY GUARANTEE.
Fault Finding Table
FAULT
POSSIBLE CAUSE
REMEDY
No hot water flow
1. Mains supply off.
1. Check and open stock cock.
2. Strainer blocked.
2. Turn off water supply. Remove strainer and
clean (see maintanance section).
3. Cold water combination valve
incorrectly fitted.
3. Check and refit as required.
Water from hot
taps is cold
1. BACK UP immersion heater not switched on.
1. Check and switch on.
2. BACK UP immersion heater thermal
cut-out has operated.
2. Check. Reset by pushing button.
3. Programmer set to Central Heating
only.
3. Check. Set to Domestic Hot Water programme.
4. Air Source Heat Pump not working.
4. Check heat pump operation. If fault is
suspected, consult heat pump instructions.
5. Thermal cut-out has operated.
5. Check. Reset by pushing button on cut-out.
Check operation of DHW thermal sensor.
6. DHW circulating pump not connected
correctly.
6. Check wiring and/or plumbing connections to
DHW circulating pump. Check isolating valves
are open.
Water discharges
from Expansion
Valve
1. INTERMITTENTLY
Expansion vessel charge pressure
has reduced below 3.5bar.
1. See Maintance section for re-charging
procedure.
2. CONTINUALLY
a. Cold water combination valve
pressure reducer not working
correctly.
b. Expansion valve seat damaged.
2a. Check pressure from cold water combination
valve. If greater than 3.6 bar, replace pressure
reducer cartridge.
2b. Remove expansion valve cartridge. Check
condition of seat. If necessary, fit new expansion
valve cartridge.
Water discharges
from T&P Relief
Valve
1. Thermal control failure. NOTE
water will be very hot.
1. Switch off power to immersion heater(s) and /or shut down
Heat Pump. DO NOT turn off water supply. When discharge
stops check all thermal controls, replace if faulty.
Milky water
1. Oxygenated water.
1. Water from a pressurised system releases
oxygen bubbles when flowing. The milkiness will
disappear after a short while.