27
Compressor Min Outdoor Temp
Enforces a minimum outside air temperature at which the
compressor will be disabled. It prevents the compressor from
running when the outdoor temperature is too low, thus resulting
in damage to the compressor. If the compressor min outdoor
temp is being enforced, auxiliary heat will be used to reach set-
point. The temperature range is adjustable from 0 to 65 °F (–17.8
to 18.3 °C) or can be completely disabled. This feature is
typically used for air-to-air source heat pumps (35 °F min
outdoor temp by default) and is disabled (by default) for
geothermal heat pumps.
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > Compressor Min Outdoor Temp.
2.
Configure the settings as required.
Note: You need an Internet connection for this feature to
operate properly.
AC Overcool Max
Uses the air conditioning to reduce the humidity by cooling
beyond the current set point by the configured amount. Note
that cooling is still determined by the set point, and the system
will not resume cooling until the temperature rises above the
current set point. For example, if your cooling set point is 75 F,
and this value is set to 2 F, it will allow the AC to overcool to 73 F
if the humidity set point has not been met.
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > AC Overcool Max.
2.
Configure the settings as required.
Aux Heat Max Temp
Configures the maximum outdoor temperature above which
the auxiliary heat will not be engaged. The temperature is
adjustable from 0 to 80 °F (26.5 °C) in increments of 0.5°F (0.3°C).
The default value is 70°F (21°C).
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > Heat Differential Temp.
2.
Configure the settings as required.
Heat Differential Temp
The minimum difference between the current temperature and
set temperature before the system calls for heat. A smaller
difference means shorter cycle times, whereas a larger
difference results in longer cycle times. The temperature range
is
adjustable from 0 to 3 °F (0 to 1.7 °C) in 0.5°F (0.3°C) increments.
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > Heat Differential Temp.
2.
Configure the settings as required.
Heat Dissipation Time
The amount of time the fan will run after the heat set point has
been reached and the call for heat has been turned off.
Running the fan for a period of time allows for any heated air
left in the ducts to circulate throughout the home. The time is
adjustable from 0 to 900 seconds. The default value is 30
seconds.
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > Heat Dissipation Time.
2.
Configure the settings as required.
Heat Min On Time
Sets the minimum equipment run time in heat mode: 1 to 20 min
(default is 5 min).
On Thermostat:
1.
Select Main Menu > Settings > Installation Settings >
Thresholds > Heat Min On Time.
2.
Configure the settings as required.