E93.1803.901 HW
42
8.1.10
P
UMP CONTROL
The applied pump must be a bronze or stainless steel pump and controlled only by the CB-HW water
heater control. If, for any reason, an external pump control is applied
without written approval of Eco
Heating systems
then the complete warranty on the CB-HW water heater and all delivered parts will
become invalid.
8.1.11
T
ANK SENSOR
The EWD300, EWD500 and EWD750 are supplied including an already assembled slice sensor (directly glued
to the SS tank behind the insulation) The sensor has an cable with a length of 5 meter.
The Strap on sensor is preferred in case an other tank is used and the self adhesive sensor cannot be applied.
Assemble the Strap on sensor to the Return pipe of the tank as close as possible to the tank. The self adhesive
sensor must be glued at the stainless steel tank at the height of the return pipe. Use an immersion bulb sensor if
one of these previous solutions are not possible.
The immersion sensor has to be fitted into an immersion pipe at 1/5 from the bottom of the tank. So at a tank with
a total height of 200 cm the sensor has to be situated at 40 cm from the bottom.
S029.000.001
Repair set self adhesive sensor
Sensor 30x40 mm Cable 5 meter.
S022.500.008
Strap on sensor.
S022.500.009
Bulb sensor
Bulb Ø 6 mm, L= 45 mm.
Cable 2 meter.
When using another type or brand sensor be sure it meets the following specifications:
NTC 10K@25°C (77 °F) B3977k 3%@60°C (140°F)
Temperature
°C (°F)
Resistance
(Ω)
Temperature
°C (°F)
Resistance
(Ω)
Temperature
°C (°F)
Resistance
(Ω)
Temperature
°C (°F)
Resistance
(Ω)
-40 (-40)
334275
10 (50)
19897
50 (122)
3599
100 (212)
674
-30 (-22)
176133
20 (68)
12493
60 (140)
2454
110 (230)
506
-20 (-4)
96761
25 (77)
10000
70 (158)
1748
120 (248)
384
-10 (14)
55218
30 (86)
8056
80 (176)
1252
130 (266)
296
0 (32)
32624
40 (104)
5324
90 (184)
912
140 (284)
230
8.1.12
S
YSTEM
S
ENSOR
.
Always use a strap-on sensor besides the immersion tank sensor. This strap-on sensor has to be connected to
connections 3-4
“System Sensor” The strap-on system sensor has part number S022.500.008 and same specifi-
cations as above mentioned.
8.1.13
R
ETURN AND
S
UPPLY PIPING OF A NON
EWD
T
ANK
To get a good mix of hot and cold water and therefore a better temperature arrangement of Water Heater and
Tank the Supply and Return pipe of the tank should be situated in the bottom 20% of the tank height preferable.
Summary of Contents for CB 105 HW
Page 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Page 70: ...E93 1803 901 HW 71...
Page 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Page 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Page 128: ...E93 1803 901 HW 129...
Page 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Page 130: ...E93 1803 901 HW 131...
Page 145: ......