Eco Air ECO1202S Installation Manual Download Page 11

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A

"

C: Putting nut on

     Remove flare nuts attached to indoor and 
     outdoor unit, then put them on pipe/tube 
      having completed burr removal.(not possible
      to put them on after flaring work) 

Flare nut

Copper tube

Fig.16

Fig.17

D: Flaring work

    Firmly hold copper pipe in a die in the 
    dimension shown in the table below.

CAUTION

Align the center of the pipes..
Sufficiently tighten  the flare 
 nut with fingers, and then tighten
 it with a spanner and torque wrench
 as shown.

Tightening Connection

Excessive  torque can  break nut 
depending on installation conditions.

Outer

diam.

Tightening

torque(N.cm)

Additional tightening

torque(N.cm)

6.35

1570

(160kgf.cm)

1960

(200kgf.cm)

4900

(500kgf.cm)

5390

(550kgf.cm)

12.7

9.53

2940

(300kgf.cm)

3430

(350kgf.cm)

Fig.19

Indoor unit tubing

Flare nut

Pipings

Fig.18

ELECTRICAL WORK

Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse
    to  install the air conditioner and explain to the client until the problem is solved. 
2. Power voltage should be in the range of 90%~110%of rated voltage.
3. The creepage protector and main power switch with a 1.5 times capacity of Max. Current
    of the unit should be installed in power circuit.
4. Ensure the air conditioner is grounded well.

 
7. An individual branch circuit and single receptacle used only for this air conditioner must be 
    available. See the following table for suggested wire sizes and fuse specifications:

5. According to the attached Electrical Connection Diagram located on the panel of the outdoor

   unit to connect the wire.

6. All wiring must comply with local and national electrical codes and be installed

   by qualified and skilled electricians.  

9

Electrical work

Outer diam.

(mm)

A(mm)

Max.

Min.

6.35

1.3

0.7

9.53

1.6

1.0

12.7

1.8

1.0

12.7

1.8

1.0

16

2.4

2.2

7360

(750kgf.cm)

7850

(800kgf.cm)

16

Summary of Contents for ECO1202S

Page 1: ...eference Before using your air conditioner please read this manual carefully and keep it for future reference Before using your air conditioner please read this manual carefully and keep it for future...

Page 2: ...ust be connected to the terminal which is marked with the letter N or coloured BLACK The BROWN wire is the LIVE and must be connected to the terminal which is marked with the letter L or coloured RED...

Page 3: ...nit by yourself Improper installation will cause water leakage electrical shock or fire Please consult authorized dealer or specialist for the installation work Please note fault caused by improper in...

Page 4: ...f the outdoor unit are not attached securely it could result in a fire or electrical shock due to dust water etc Perform electrical work according to the installation manual and be sure to use an excl...

Page 5: ...Outdoor unit If an awning is built over the outdoor unit to prevent direct sunlight or rain exposure make sure that heat radiation from the condenser is not restricted Ensure that the clearance aroun...

Page 6: ...minimise vibration excessive noise The indoor unit should be installed on the wall at a height of 2 3 metres or more from the floor Two of the A B and C directions should be free from obstructions CA...

Page 7: ...allation plate Dimensions are in mm unless otherwise stated Wall Indoor Outdoor 5 7mm Fig 6 INSTALLATION INSTRUCTIONS A 40 B Right rear side refrigerant pipe hole 65 Installation plate Indoor unit out...

Page 8: ...rom side to side to see that it is securely hooked 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping...

Page 9: ...hose sloped downward to drain out the con densed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction wher...

Page 10: ...o defect in the flaring work Carry out correct flaring work using the following procedure A Cut the pipes and the cable 1 Use the piping kit accessory or pipes purchased locally 2 Measure the distance...

Page 11: ...RK Electric safety regulations for the initial Installation 1 If there is serious safety problem about the power supply the technicians should refuse to install the air conditioner and explain to the...

Page 12: ...10 Electrical work Fig 20 Fig 21 Electrical control box cover Panel 10mm 10mm 40mm 40mm Cooling only type Cooling heating type Code wire Or 10mm 40mm Cooling heating type Terminal block of indoor uni...

Page 13: ...cure the cable onto the control board with the cord clamp 1 Remove the electrical control board cover from the outdoor unit by loosening the screw 2 Connect the connective cables to the terminals as i...

Page 14: ...hall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION AIR PURGING Air and moisture in the refr...

Page 15: ...of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose the flare nut of the Lo valve on the gas pipe side and check that the air is entering Operation no...

Page 16: ...ck 1 Soap water method Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of th pi...

Page 17: ...MEMO Date of installation Purchased from Dealer Name Date of purchase Model number Serial number...

Page 18: ...ing from a faulty installation is specifically excluded This unit must be operated under conditions as recommended at voltages indicated on the unit Any attempts made to service or modify the unit by...

Reviews: