Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk
outputs.
Note: Water Pump control in antifreeze protection will never be blocked.
16.6. Insufficient Water Flow Protection
All outputs will be closed if water flow is insufficient or the water flow switch is malfunctioning.
System uses two approaches to check whether the water flow is insufficient.
Water Flow Switch
System will check the state of Water Flow Switch one minute after the water pump is on. Insufficient water flow protection will
be activated if the switch is observed to be disconnected for a continuous 10 seconds.
Water Temp Difference between Inlet and Outlet
When inlet/outlet water temperature difference is bigger than P12, insufficient water flow protection will be activated.
16.7. High/Low Pressure Protection
1) High Pressure Protection
:
If the High Pressure Switch is observed to be disconnected, High Pressure Protection will be
activated and the corresponding compressor will be shut down.
2) Low Pressure Protection: When the Low Pressure Switch is observed to be disconnected for a continuous 10 seconds, the
corresponding compressor will be shut down.
(Low Pressure Protection will be blocked in the first three minutes in heating mode, in the first 30 seconds in cooling mode
and in defrosting state.)
Error Code
Input Port
Error Description
Code
Results
01
Inlet Water Temp Sensor
Malfunction
E1
Close All Outputs
02
Outlet
Water
Temp
Sensor Malfunction
E2
Close All Outputs
03
Ambient Air Temp Sensor
Malfunction
E3
Close All Outputs
04
Evaporator Coil Temp
Sensor 1 Malfunction
E4
Close All Outputs
05
Evaporator Coil Temp
Sensor 1 Malfunction
E5
Close All Outputs
06
FLOW
Insufficient Water Flow
( Water Flow Switch
Malfunction
or
Water
Temp Diff too Big)
E6
Close All Outputs
07
HP1
High Pressure Protection
Compressor 1
E7
Shut Down Compressor
1
08
LP1
Low Pressure Protection
Compressor 1
E8
Shut Down Compressor
1
09
HP2
High Pressure Protection
Compressor 2
E9
Shut Down Compressor
2
10
LP2
Low Pressure Protection
Compressor 2
E10
Shut Down Compressor
2
11
Hot Water Temp Sensor
Malfunction
E11
Close All Outputs
12
OV1
Compressor 1 Overload
E12
Shutdown Compressor
1