104
0 .0 °C ( 0 °F )
T 1 - T d + 1 . 5 °C ( 3 4 .7 °F )
L
( H + - L ) * 0 .2 + L
( H + - L ) * 0 .4 + L
( H + - L ) * 0 .6 + L
H +
( H + - L ) * 0 .8 + L
- 1 °C ( - 1 .8 °F )
- 2 °C ( - 3 .6 °F )
- 3 °C ( - 5 .4 °F )
- 4 °C ( - 7 .2 °F )
- 5 °C ( - 9 °F )
- 6 °C ( - 1 0 .8 °F )
- 6 .5 °C ( - 1 1 .7 °F )
15.4.3.3 Defrosting mode
If any one of the following items is satisfied, AC
will enter the defrosting mode.
After the compressor starts up and keeps
running, mark the minimum value of T3 from
the 10th minutes to 15th minutes as T30.
1)If the compressor cumulate running time is up
to 29 minutes and T3< TCDI1, T3
+
T30SUBT3ONE
≦
T30.
2)If the compressor cumulate running time is up
to 35 minutes and T3< TCDI2, T3
+
T30SUBT3TWO
≦
T30.
3)If the compressor cumulate running time is up
to 29 minutes and T3< TCDI3 for 3 minutes.
4)If the compressor cumulate running time is up
to 120 minutes and T3<-15
℃
(5°F).
Condition of ending defrosting:
If any one of the following items is satisfied, the
defrosting will finish and the machine will turn to
normal heating mode.
----T3 rises to be higher than TCDE1.
----T3 keeps to be higher than TCDE2 for 80
seconds.
----The machine has run for 10 minutes in
defrosting mode.
Defrosting action
:
Compressor
Outdoor fan
4-Way valve
X1 10S
10S
no longer than 10min
X2
15.4.3.5
Evaporator
coil
temperature
protection
T E s to p
T 2
R e s u m e
O ff
D e c r e a s e
T E d o w n
T E H 2
H o ld
Off: Compressor stops.
Decrease: Decrease the running frequency to
the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
15.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17~30
℃
(63~86°F).
In auto mode, the machine will choose cooling,
heating or fan-
only mode according to ΔT (ΔT
=T1-Ts).
ΔT=T1-Ts
Running mode
ΔT>2
℃
(3.6°F)
Cooling
-2
℃
(-3.6°F)
≤ΔT≤2
℃
(3.6°F)
Fan-only
ΔT<-2
℃
(-3.6°F)
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for 15 minutes and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
15.4.5 Drying mode
Drying mode works the same as cooling mode
in breeze speed.
All protections are active and the same as that
in cooling mode.
15.4.6 Timer function
Summary of Contents for CTBU-09HWFN1-M(C)
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units...
Page 9: ...6 A5 Duct Units A6 Duct Units...
Page 10: ...7 Console Units...
Page 11: ...8 Ceiling floor Units...
Page 12: ...9 HESP DUCT Units...
Page 21: ...18 2 3 4 7 Outside Water Pump for Optional When Ceiling Installation...
Page 29: ...26 Console Units 1 6 D ra in p ip e 1 9 5 H a n g in g a rm U n it m m 7 0 0 6 0 0 2 1 0...
Page 36: ...33 Console Units Ceiling floor Units...
Page 41: ...38 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Page 42: ...39 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Page 43: ...40 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Page 44: ...41 MUE 48HRFN1 M C MUE 60HRFN1 MW...
Page 45: ...42 MUE 36HRFN1 M C MUE 48HRFN1 M C...
Page 46: ...43 MUE 60HRFN1 MW MTIU 09HWFN1 M MTIU 12HWFN1 M MTIU 18HWFN1 M MTIU 24HWFN1 M...
Page 49: ...46 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Page 50: ...47 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Page 51: ...48 MOD30U 36HFN1 M...
Page 57: ...54 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 58: ...55 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 59: ...56 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 60: ...57 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 61: ...58 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 62: ...59 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 78: ...75 12 Field Wiring 9K 24K 36K 48K 60K...
Page 79: ...76...
Page 129: ...126 P U P V...
Page 130: ...127 P W P N...
Page 147: ...144...
Page 193: ...190 5 Remove the four fixing screws of the fan motor then remove the motor 5...