Modbus Read, Write and Override Parameters plus Exception Codes
104
UDC2500 Universal Digital Limit ControllerProduct Manual
8/05
Table 10-7 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Options.
Table 10-6 Set-up Group – Options
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Auxiliary
Output
009E 158
INT R/W 0 = None
1 = Not Used
2 = Not Used
3 = PV
Low Scaling
Factor
0031
049
FP
R/W
Within the range of the
selected variable in ID 134
158
High Scaling
Factor
0032
050
FP
R/W
Within the range of the
selected variable in ID 134
158
Auxiliary
Output Range
00EC 236
INT R/W
0 = 4-20 mA
1 = 0-20 mA
Digital Input
#1 (External
Reset)
00BA 186
INT R/W
0 = None
1 = Enable
2 = External Reset Only