background image

4

Eclipse AirHeat v1.0 - Installation Guide No. 140,  11/4/03

2.0

Control System Requirements

Turndown Method

Input is normally controlled by a motorized butterfly valve in the gas line to the
burner.

Regulator Loading Lines

Connect the top diaphragm chambers of the main gas and pilot gas regulators to the
duct approximately 10" downstream of the burner. This will allow the regulators to
maintain a constant supply pressure to the burner regardless of varying pressures in
the duct.

Piloting

Pilot gas flow is adjusted as shown in Figure 6.

Ignition

Ignition voltage should be 6000 VAC.

Check Valve

See Figure 3. At high fire, the gas pressure at the burner inlet is higher than the air pressure, and
the check valve is closed. At low fire, gas pressure falls below the air pressure, and the check
valve opens, permitting a small amount of air to mix with the gas. This premix at low fire stabilizes
the flame and helps distribute the flame evenly down the length of the burner.

Do not install any valve or controlling device in the gas line between the
burner and the check valve tee, Figure 3. Because this section of the gas
line carries a partial pemix at low fire, it is possible under unusual condi-
tions for the flame to travel back through the pipe to the tee. Devices in-
stalled in this section may be damaged and may melt, releasing gas to the
atmosphere and causing fires or explosions.

Pressure Switch Connection

See Figure 4 for typical connection of combustion air and circulating fan limit
switches.

Limit Controls &Safety Equipment

Limit controls and safety equipment should comply with current NFPA Stan-
dards* 86 and 86C, and all applicable local codes and/or standards.

*Available from:

National Fire Protection Association

American National Standard Inst.

Batterymarch Park

1430 Broadway

Quincy, MA 02269

New York, New York 10018

Figure 3–Check Valve Operation

Figure 4—Pressure Switch Location

w

Warning

Gas Inlet

Manifold

Check Valve Opens When

Gas Inlet Pressure Is at Low Fire

Process Air

WARNING!

Do Not Install Any Valves Here!

See Section 2.0

Tee

P

Hi

Lo

Blower

Pressure Switch

P

Lo

Hi

Circulating Air

Pressure Switch

Tube Points

Upstream

Tube Points

Downstream

Tube at

Blower Inlet

Burner Air Tap

See Figure 7

Summary of Contents for AH

Page 1: ...eviate from any in structions or application limits in this Guide without written advice from the Eclipse Combustion Division in Rockford Illinois Read this entire Guide before at tempting to light bu...

Page 2: ...stion air blower mounted on the back of the burner s steel case By supplying the correct air volume and pressure to the burner the blower allows stable operation over a wide range of duct veloci ties...

Page 3: ...me monitoring endplate see Data 140 6 to mount a second flame rod on the end op posite the gas inlet Motor Standard 230 460 3 60 TEFC Other motors can be supplied Materials All portions of the burner...

Page 4: ...device in the gas line between the burner and the check valve tee Figure 3 Because this section of the gas line carries a partial pemix at low fire it is possible under unusual condi tions for the fl...

Page 5: ...o nearest point of possible flame impingement at an input of 1 000 000 Btu hr 962 kW m On burners longer than 36 914 mm use a hanger or a pedes tal to support the blower and motor Duct Lengths Min Max...

Page 6: ...e NFPA Std 70 or ANSI CI 1981 or must be acceptable to the authority having jurisdiction Available from National Fire Protection Association American National Standard Inst Batterymarch Park 1430 Broa...

Page 7: ...toring signal strong enough to reliably open the gas shut off valves Set Gas Flow Measure the gas differential pressure as shown in Figure 7 With the gas control valve at low fire open all main gas va...

Page 8: ...open determine if an effective d Clean check valve pressure is being trans e Too much pilot gas mitted to regulator e Reduce pilot gas flow 5 Flame failure when main a Gas pressure to pilot a See Che...

Reviews: