3-3/16"
81 mm
Optional
Adaptor
#03428
210 JIB-F & 236 JIB-G Burner
Optional
10
°
Adaptor
10
°
6-1/8" Sq.
156 mm
Mtg. Holes (4)
1/2" Dia. (13 mm)
5-1/8" Sq.
130 mm
Mounting Flange Detail
3
3.0 Installation
WARNING
If improperly adjusted or operated, burners can
produce toxic concentrations of gases, including
carbon monoxide. Venting these products into
confined, poorly ventilated areas is dangerous. To
avoid this situation:
• Vent the appliance to the outdoors wherever
feasible. See the appliance manufacturer's in-
struction manual for flue and stack design guide-
lines.
• Where equipment location or other considera-
tions prevent outside venting, be sure that the
building has adequate volume and fresh air
makeup to dilute any potentially harmful com-
bustion products down to safe levels as defined
by OSHA or other authorities having jurisdiction.
3.1 Burner Inspection
Make a thorough inspection of the burner when
uncrating and before installing it. If any parts ap-
pear broken, bent, or damaged, contact your Eclipse
representative or the Eclipse factory before install-
ing the burner.
3.2 Burner Environment
Protect burners from the weather.
Combustion air should be free of contaminants
which might corrode or plug the blower or burner's
internal passages.
Provide access to the burners for inspection, main-
tenance and removal.
Any obstruction placed directly in front of the
burner will overheat and damage the burner.
3.3 Burner Mounting
See Figure 3 for mounting details. Do not over-
tighten the mounting bolts, as excessive force on the
flange may break the casting.
For maximum service life of the automatic gas shut-
off valves, mount the burner in the orientation
shown in Figure 3.
3.4 Burner Piping
Connect the gas supply line to the burner and make
certain the supply line is adequate in size. For long
runs, the pipe size should be larger than the burner
inlet to prevent excessive losses. Check with your
gas company if in doubt.
For convenience in burner removal, Eclipse rec-
ommends installing a shutoff cock and suitable
pipe union dsconnect upstream of the burner.
Use flexible nipples on all gas connections. Solid
piping may restrain the burner from normal thermal
expansion and damage the burner or its piping com-
ponents. Do not use the burner assembly to support
the piping.
Gas piping must comply with American National
Standard “National Fuel Gas Code” (NFPA No. 54
or ANSI Z223.1)*, or must be acceptable to the au-
thority having jurisdiction.
3.5 General Wiring Suggestions
The electrical supply must be 120 volt, 60 cycle,
single phase AC. Make all electrical connections in
accordance with the appropriate wiring diagram in
Figure 2.
Do not
disturb the factory installed wiring. Contact
the Eclipse factory regarding special operating se-
quences and controls. Install suitable main discon-
nect switch and fuses at a convenient location. Be
certain that the ignition cable is properly connected
to the spark plug and the pilot ignition transformer.
Electrical wiring must comply with the National
Electric Code*, (NFPA Std. 70 or ANSI-CI 1981), or
must be acceptable to the authority having jurisdic-
tion.
*Available from:
National Fire Protection Association
Batterymarch, Park
Quincy, MA 02269
American National Standard Institute
1430 Broadway
New York, NY 10018
6
10-1/2"
267 mm
6-5/8"
168 mm
23"
584 mm
7-9/16"
193 mm
2-3/4"
70 mm
O.D.
4-1/2"
114 mm
12-1/4"
311 mm
Gas
Adjusting
Screw
1
2
9
7
12
8
10
11
3
6
5
4
Gas Inlet
1" N.P.T.
Tap “B”
1/8" Pipe Plug on
Opposite Side
of Inlet Cock
Air
Shutter
Figure 1
Dimensions & Parts List
Item
Function
Description
210 JIB-F
236 JIB-G
1
Manual Gas Cock
Essex
19122
19122
2
Automatic Gas Shut-Off
Eclipse Solenoid
13250
13250
3
Automatic Gas Shut-Off
Eclipse Solenoid
13250
13250
4
Manual Gas Cock
Essex
19122
19122
5
Automatic Pilot Valve
Eclipse Solenoid
16728-1
16728-1
6
Adjustable Pilot Cock
---
12659
12659
7
Air Flow Switch
SMDF-12C133
14494
14494
8
Ignition Transformer
RA-890G or PCI UV
1/2 Wave Transformer
13551
13551
All other burners
612-6A020E
12178
12178
9
Flame Monitor
10
Flame Sensor
11
Spark Plug
---
16946-6
16946-6
12
Blower Motor
See “Specifications”
11366
12995
See model under “Specifications.”