6 Installation and start-up of VS 3015 C
The system centre, the operator terminal and the PC software LDSWin are used for the configuration of the
controller for the start-up and for later changes.
Furthermore, actual values and archived long-term data can be displayed. Basic hardware and software
settings must be made on the pack controller before the start-up of the system.
6.1 DIN rail mounting
The pack controller is available as version for DIN rail mounting. It is snapped on / fastened to the DIN rail using
two claws (on the underside of the device). The power loss of the device is 24 VA. This must be taken into
account for the installation. The pack controller can be put into operation after completion of the mechanical
and electrical installation.
6.2 Requirements for the activation of NT CO2 operation (transcritical)
•
Type identification
must
be VS 3015 C, i.e. the correct firmware must be loaded (see chapter
•
The 4th digit of the serial number
must
be "1", e.g.
111
1
0000031002
(see menu 2-3 on the system
centre or menu 7-2 -
Status display -
of the store computer or operator terminal)
•
R744 (CO
2
) is always preset as refrigerant
Important safety instructions!
Before the installation and start-up of the controller, the complete
must be read carefully and all safety instructions and hazard warnings must
be observed. Any maintenance by the user is not intended as possible hazards from incorrect re-
assembly cannot be ruled out. Opening the device is not authorised! Furthermore, it must be noted that
the safety of the system or the installation in which the device is integrated is the responsibility of the
creator of the system or installation. If the device is used in any way not specified by Eckelmann AG,
the protection supported by the device can be compromised!
The controller should only be used with compatible versions of the PC software LDSWin, otherwise the
scope of functions can be restricted.
Tip
: The
The pack controller may only be mounted on a DIN rail and operated as an integrated regulation and
control device (EN60730). All supply lines from and to the device (with the exception of the 230 V
power supply and signal lines) must be shielded! This particularly applies for the analogue inputs
(sensor supply lines) as well as for the CAN bus cabling (cable type: LiYCY (TP)). These must also be
installed with sufficiently large distance from live cables. This prevents faulty measurements and
protects the device against electrical interference via the analogue inputs.
Protection type and dimensions can be found in the chapter
Technische Daten VS 3010 C / SIOX
.
All the above mentioned conditions
must
be met, otherwise the controller behaves like a VS 3010!