Operation of VS 300
89
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
7.12 Manual control / Service mode (Parameter List C)
Parameter List C takes you to service mode. In check (service) mode, all analog outputs and the digital relay/
control stages can be actuated manually. First, the two controllers are deactivated or all relay/control stages are
unloaded. During this time, a moving light on the display signals that the controllers are deactivated. The param
eters specified in Parameter List C can then be used to adjust the corresponding outputs as required (see sec
tion 7 Parameter List and Menu Structure – Parameter List C).
Setpoints can only be changed at the Setpoint Adjustment Enabled access level (see section 7.7
Changing the Access Level). The LED display flashes to indicate when values (setpoints) can be
changed.
7.13 Displaying reported faults (Parameter List F)
Parameter List F takes you to a list of messages. Faults and messages are displayed in two ways:
1.
In basic display mode:
The respectively most recent message is indicated in basic display mode by its
associate fault code (
E001
−
E246
, see section NO TAG Process Fault Reports or System Fault Reports
for details). The alarm/message LED flashes. Pressing the ESC/RESET key quit the display and returns to
displaying control loop actual temperature. When the message is no longer current or when no more faults
are effective, press the ESC/RESET (longer than 5 sec.) to cancel the message and delete it from the fault
report memory.
2.
In message display mode:
From Parameter List F you can change to message display mode. On press
ing the
↵
key while in Parameter List F,
F001
is displayed if a message is current, meaning not yet can
celled. This indicates the most recent message. Use the
↑
key to move to the preceding messages (
F002
to max.
F100
). If no messages exist, '- - - -' is shown on the display.
Messages that are still current flash to distinguish them from those no longer current.
Pressing the
↵
key again while in message display mode (
F002
- max.
F100
) displays details of the selected
message. The details consist of the message code (
E001 -
.
E246
, see section 8 Process Fault Reports or Sys
tem Fault Reports for details), message status (0 or 1), the incoming time stamp (date-year-time) and outgoing
time stamp (date-year-time). Use the
↑
and
↓
keys to view these message details. The status LEDs of the relay/
control stages illuminate to indicate which message detail is currently displayed.
Status LED
Message details displayed
1
Message/alarm code:
E001...E246 - For details see section 10.5 Message Types
Menu Structures - Parameter List F or section 10.5 System/
Process Fault Reports
2
Message/alarm code:
0: Message not active
1: Message active
3
4
5
6
7
Receive time stamp:
Day
Receive time stamp:
Month
Receive time stamp:
Year
Receive time stamp:
Hour
Receive time stamp:
Minute
8
9
10
11
12
Send time stamp:
Tag
Send time stamp:
Month
Send time stamp:
Year
Send time stamp:
Hour
Send time stamp:
Minute
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...