Parameter List and Menu Structure of VS 300
109
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
Controller configuration must be made prior to making individual parameter settings, as first start is
performed after changing configuration!
In first start, default settings are loaded for all parameters and all archives (alarms and operating
data, e.g. run times, starts, activity) are deleted!
8.1.11 Parameter List S4: Setpoints Alarm Priorities
Parameter
No.
Alarm priorities for:
Range
Default
Displayed /
Condition
NT
LT
HP
S400
High pressure CL1
-: Not recorded
0: Only entered in report list
1: Alarm priority 1
2: Alarm priority 2
2
2
2
Always shown
S401
High pressure CL2
2
2
2
S402
Low pressure CL1
2
2
2
S403
Low pressure CL2
2
2
2
S404
Pressure measuring
loop error CL1
2
2
2
S405
Pressure measuring
loop error CL2
2
2
2
S409
Service mode active
0
0
0
S410
Load shedding activa
ted
0
0
0
S411
Fast unload activated
0
0
0
S416
Setpoint changed
0
0
0
S417
Controller configura
tion changed LT, NT,
HP
0
0
0
S418
External alarm via di
gital inputs 1 - 4
2
2
2
S419
S420
S421
S422
Sensor type changed
2
2
2
S430
Power failure/restart
0
0
0
S431
First start
2
2
2
S432
Low battery
2
2
2
S433
Internal error
2
2
2
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...