Parameter List and Menu Structure of VS 300
105
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
8.1.7
Parameter List S2: Common Setpoints
Parameter
No.
Function/
Description
Range
Dim.
Displayed / Condition
S280
Current time, hour
0..23
Hour
Always shown
S281
Current time, minute
0..59
Minutes
S282
Current date, day
1..31
Day
S283
Current date, month
1..12
Month
S284
Current date, year
1900..2155
Year
S285
Adjustment for daylight
saving time changes
0:
Not adjusted
1:
Adjusted
-
S290
CAN bus adress
---, 101..109
-
Date and time only need to be set, and only can be set, in stand-alone operation! When the VS 300 is
connected via CAN bus module to a master clock (CI 3000 Store Computer or AL 300 Operator Termi
nal), the date and time will be supplied by this master and applied to the VS 300, meaning that they
then cannot be changed.
Parameter List S2:
To change values set access level to
setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
8.1.8
Parameter List S3: Setpoints System Configuration
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
(1): Minimum of one stage must
be defined in CL:
CL1:
S301
>
0
CL2:
S331
>
0
NT
LT
HP
S300
S330
Control type
0: Step control
1: Speed control
2: Combined control
0
0
0
-
(1) and
only
available in con
junction if CL is configured as
HP controller
S301
S331
Number of base load
stages
S300/330=0:
0 - max
1)
S300/330=1:
1 or 2
S300/330=2:
min 2 - max
1)
2/4/8
2)
-
Always shown
S302
S332
Number of capacity
stages each base
load stage
S300/330=0:
1 - 3
1)
S300/330=1:
= 1
S300/330=2:
= 1
1
1
1
-
(1)
Only
available in conjunction
with step control!
S303
S333
Number of capacity-
controlled base load
stages
S300/330=0:
0..
[
Value S301/331
]
1)
S300/330=1:
= 0
S300/330=2:
= 0
0
0
0
-
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...