Parameter List and Menu Structure of VS 300
100
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
8.1.1
Parameter List A: Actual Values System Data
CL1
CL2
Function/
Description
Range
Dim.
Displayed / Condition
(1): Minimum of one stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
A000
A010
Actual value / Pressure
1)
bar
Always shown
A001
A011
Setpoint / Pressure
bar
(1)
A002
A012
Actual value /
Temperature
°C
A003
A013
Setpoint / Temperature
°C
A004
A014
Controller output
Analog output
0..100
%
(1), an CL not step-by-step switch:
CL1:
S300
>
0
/ CL2:
S330
>
0
A005
A015
Temperature setpoint
for setpoint shift
1)
°C
(1), and temperature shift must be activated in CL1: S310 = 1 /
CL2: S340 = 1
A06
A016
Actual value Hunidity
1)
%
(1), and humidity shift must be activated in CL1: S311 = 1 /
CL2: S341 = 1
1)
Range depends on controller configuration (see Parameter List
S3
) and operating mode!
8.1.2
Parameter List A: Common Actual Values System Data
CL 1 / CL 2
Function/
Description
Range
Dim.
Displayed / Condition
(1): Minimum of one stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
A020.[1]
..
A020.[m]
and
A020.[n]
..
A020.[o]
Operating hours of relay
stages 1 - 12
2)
0..29999
3)
h
CL1: S301 > 0
[m]=
Basic configuration (<=4):
[
Value
S301
]
1st expansion (<=8):
[
Value
S301
]
2nd expansion (<=12):
[
Value
S301
]
CL2: S331 > 0
[n]= [
Value
S301
] + 1
[o]=
Basic configuration (<=4):
[n] + [
Value
S331
]
1st expansion (<=8):
[n] + [
Value
S331
]
2nd expansion (<=12):
[n] + [
Value
S331
]
A030
Status digital input
I1 - I4
4)
0 / 1 = Actuated
-
Always shown
A035
Status Alarm output
A1 and A2
5)
0 / 1 = Actuated
-
A051
Version no. [x.y]
1.3x
-
A060
Enter password
Change access level
0:
Setp. adjust.
not enabled
1:
Setp. adjust-
ment enabled
10:
Superuser
mode
-
2)
Number of relay stages CL1 [
Value S301
] + Number of relays CL2 [
Value S331
] + number internal alarm
relay <= Number of relay stages VS 300 (varying with expansion stage/number of relay stages can be 4/8/12)
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...