Operation of UA 410 D
68
Firmware V1.40 - Doku 2.1 06. April 2016
7.2
Local operation with a BT 300 x operator interface
BT 300 x
ESC
RESET
DISPLAY
An operator interface in the BT 300 series is connected locally via the DISPLAY interface. Thereby, the con
troller can be operated standalone as shown or also connected to the CAN bus.
The operation here largely corresponds to the possibilities as described for the system centre, the store com
puter and the operator terminal; see chapter 7.3.1 for details.
If no buttons are pressed, the display of the BT 300 x operator interface shows the name of the controller and its
position designation. The ENTER button (
↵
) must be tapped to return from the display of the operating status
back to the Operation menu.
Device-specific limitations arise due to the smaller display (only 2 rows x 20 characters) and fewer
buttons as compared with the system centre, the store computer and operator terminal.
Operation with a system centre, store computer, operator terminal or the PC software LDSWin pro
vides more functional possibilities.
Technical details about the operator interfaces can be found in their operating instructions
.
7.2.1
Lock-down of the setpoint change
The operator interfaces of the BT 300 series can be locked using a jumper on the circuit board so that all actual
values, parameters, temperatures and statuses can be viewed, but so that it is no longer possible to adjust the
setpoints of the respective controller.
F
P
P
.N
r
.
ZNR. 110 230 DEF0
Jumper (A)
6
5
4
3
2
1
Jumper (B)
Jumper setting A:
with setpoint change
Jumper setting B:
without setpoint change
The operator interfaces are set to the jumper position A (with setpoint change) at the factory.
If operator interfaces are mounted in areas accessible to the public, i.e. on serving counters for the
sales personnel, the jumper position
B
should be selected (without setpoint change).
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...