change (2 second lag time) if you move the sensor to areas with different 

light levels. See blink indicator table on the next page.

LIGHT LEVEL TEST TABLE

The green LED will blink according to the energy produced by the solar cell

Blinks

Lux 

Foot Candles

Charge Level

0

0

0

below operating level

1

50-100

4.5 to 9

min. operating level

2

100-200 

9 to 18

operational

3

200-400 

18 to 36

operational

4

400-800 

36 to 72

operational

5

800+ 

72+

operational

The test will repeat every 2 seconds and run for a duration of 100 seconds. You 

may quit the test at any time by pressing the Test button for 10 seconds.

Range  Confirmation  Test:

  provides  visual  feedback  of  the  sensors  signal 

strength by a linked receiver with range confirmation capability (only “F series” 

controllers have range confirmation ability). Have only one receiver linked to the 

sensor for proper operation of the test and disable repeaters in range for proper 

test operation).

The Range Confirmation test requires a battery to be installed.

1. 

To enter Range Confirmation Test mode, press and hold the test button for 

6 seconds. The green LED will begin to blink.

2. A quick press and release of the button at this point will allow you to select 

between test modes. Pressing and releasing the test button scrolls through 

the LED indicators. When the amber LED is blinking, go to step 3. 

3. 

Press and hold the test button again for 6 seconds to select Range 

Confirmation Test. 

4. All three LED’s will blink (for 1 second) in this test mode when the sensor 

transmits or receives a Range Confirmation Telegram followed by the 

sensor displaying the linked signal strength status for 2.5 seconds.

RANGE CONFIRMATION TEST TABLE

LED

Signal Strength

Green - Blinking 2.5 sec

-41 to -70 dBm 

Amber - Blinking 2.5 sec

-70 to -80 dBm

Red - Blinking 2.5 sec

-80 to -95 dBm

No LED

No linked receivers detected

T

he test will repeat every 4 seconds and run for a duration of 50 seconds. You 

may quit the test at any time by pressing the test button for 10 seconds.

Walk Test Mode

: In walk test mode, the red LED will blink on every motion event. 

This allows an installer to verify the sensor can monitor and detect motion in an 

area as required.

1. 

To enter Walk Test mode, press and hold the Test button for 6 seconds. The 

green LED will begin to blink.

Summary of Contents for RVS-A-xW

Page 1: ...te the cover must be fully seated for proper operation Resonate Vacancy Occupancy Sensor Description The RVS RCS also referred to as the sensor in this guide is a wireless energy harvesting sensor tha...

Page 2: ...motion is detected the sensor will transmit an occupied telegram If no motion is detected within 100 seconds the sensor transmits a vacancy telegram 200 seconds total since the previous transmission T...

Page 3: ...nts as hot moving air may cause the sensor to false trigger Leave at least 4 1 2 m minimum between air vents and the sensor NOTE Incandescent lights may cause false trips when turning on 1 Select a lo...

Page 4: ...s mounting plate iii Poke the adapter tines through the ceiling tile then bend each tine over in opposite directions for a secure fit iv Replace the ceiling tile With double sided tape or Velcro not p...

Page 5: ...small screwdriver as a lever and insert under the battery Gently twist the screwdriver so the battery pops out 3 Install or replace the battery with a new CR1632 coin cell battery insuring the positi...

Page 6: ...ode press and hold the test button for 6 seconds The green LED will begin to blink 2 A quick press and release of the button at this point will allow you to select between test modes Pressing and rele...

Page 7: ...o to step 2 2 Press and hold the test button again for 6 seconds to select PIR sensitivity adjust mode One of the LEDs will begin blinking based on the selected settings see the Sensitivity Adjust Tab...

Page 8: ...8 733 0111 Fax 604 815 0078 Email info echoflexsolutions com www echoflexsolutions com Copyright 2015 2017 Echoflex Solutions Inc Specifications subject to change without notice Document 8DC 5543 Revi...

Reviews: