Echoflex Installation Guide
Emergency Bypass Load Controller
5. Connect the normal sense wiring leads.
a. Connect the
Normal Power Sense
[Black 1 mm
2
(18 AWG)] and
Normal Switch Sense
[Red 1 mm
2
(18 AWG)] wiring leads to the
normal lighting circuit .
Note:
To ensure that the emergency lighting in the controlled
area turns On in the event of a power loss, you must connect the
Normal Power Sense wires upstream of any switched control
device for the normal lighting loads.
b. Connect the
Normal Neutral
[White 1 mm
2
(18 AWG)] lead to the
normal Neutral for the lighting loads.
6. Are you are installing a remote triggering device to remotely activate
the emergency circuit?
•
No: Go to
to confirm the connection.
•
Yes: See
for wiring instructions.
7. Replace the cover plate and restore power to the circuits.
Wiring Diagram
Emergency Bypass
Load Controller EREB-AP
Remote
LED
Option
Button
Status
LED
Emergency Power In (Black 4 mm²)
Emergency Power Out (Red 4 mm²)
Emergency Neutral (Gray 1 mm²)
Normal Power Sense (Black 1 mm²)
Normal Switch Sense (Red 1 mm²)
Normal Neutral (White 1 mm²)
Normally Closed:
-Test Switch
-Fire Alarm Panel
-Security System
Remote Activation Input
The EREB-AP offers a normally closed, dry contact input to accommodate
connection to a fire alarm panel, security system, or test switch. This
input ships from the factory with a blue wire loop (jumper) on the side of
the device. It is a complete loop that disables remote activation. Do not
cut this jumper unless you are installing a remote triggering device.
Note:
Echoflex recommends that you power up and test your
system before connecting to a remote device.
Emergency Bypass Load Controller
Page 4 of 12