Echoflex Installation Guide

Dual Tech Ceiling-mount Vacancy Sensor

Installation

Installation should follow all local codes and standard electrical practices.

Note:

NEC Class 2 product to be wired in accordance to NEC Article

725 and local jurisdiction requirements.

The ceiling-mount sensor is provided with a mounting plate that can be
mounted to a junction box, finished ceiling, or soft ceiling tile. Determine the
installation method and follow the detailed instructions:

Junction Box or Surface Installation below

Soft Ceiling Tile Installation on the facing page

Junction Box or Surface Installation

1.

Pull the Belden 8471 (or
equivalent) and one 14 AWG
(2.5 mm

2

) ground wire to the

mounting location (junction
box or finished surface) and
strip each wire 3/8” (9–
10 mm).

2.

Temporarily remove the
sensor cover to gain access to
the configuration switches
and mounting access holes.
Hold the sensor in one hand
while gently twisting the
cover clockwise.

3.

Connect the EchoConnect
wires from the sensor to the
installed wires.

a.

Connect the data - (typically black) EchoConnect wire from
sensor to the incoming EchoConnect (typically black) wire using a
WAGO wire termination connector.

b.

Repeat the above step for the data + (typically white)
EchoConnect wire and for the ESD ground wire, using a new
WAGO connector for each termination type.

4.

Orient the flat side of the sensor to the junction box or surface and
secure it in place using the screws provided (both short and long
screws are provided for installation convenience).

Dual Tech Ceiling-mount Vacancy Sensor

Page 4 of 12

Echoflex Solutions, Inc.

Summary of Contents for Elaho Dual Tech Ceiling-mount Vacancy Sensor

Page 1: ...tionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black fi...

Page 2: ...al attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixt...

Page 3: ...devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cabl...

Page 4: ...location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Page 5: ...hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinho...

Page 6: ...nctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space...

Page 7: ...e ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On...

Page 8: ...eout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic d...

Page 9: ...s If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period afte...

Page 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Page 11: ...10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20...

Page 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc...