Chengdu Ebyte Electronic Technology Co.,Ltd.
【4AI+4DO】MA02-XACX0440
User Manual
Copyright ©2012–2021
,
Chengdu Ebyte Electronic Technology Co.,Ltd.
33
0000
current level signal of DI.
(41204)0x
04B4
4
DI count value
RW
0x0001-0x0008,
writing
means the initial value of
the set count, reading
means reading the already
counted value.
0x03
、
0x06
、
0x10
(41400)0x
0578
4
DO
working
mode
RW
0x0000-0x0002, 0x0000
level mode (default mode),
0x0001
pulse
mode,
0x0002 follow mode.
0x03
、
0x06
、
0x10
(41500)0x
05DC
4
DO pulse width
RW
0x32-0xFFF (50-65535),
the duration of the pulse,
in ms.
0x03
、
0x06
、
0x10
(41318)0x
0526
4
DI
counting
method
RW
0x0000-0x0002, 0x0000
means rising edge count,
0x0001 means falling edge
count, 0x0002 means level
count.
0x03
、
0x06
、
0x10
(41304)0x
0518
4
DI count value
clearing method
RW
0x0000-0x0001,0x0000
automatic clearing mode,
0x0001 manual clearing.
0x03
、
0x06
、
0x10
(41311)0x
051F
4
Set the clearing
method
RW
0x0001-0x00FF
。
0x03
、
0x06
、
0x10
(41600)0x
0640
4
Set DO follow
channel
RW
0x0001-0x0008, 0x0001
represents the first input.
0x03
、
0x06
、
0x10
(42000)0x
07D0
7
Module model
R
See model definition table. 0x03
(42012)0x
07DC
2
Firmware version
R
Firmware version number. 0x03
(42014)0x
07DE
10
Module name
RW
The name can be up to 20
bytes long, including "\0".
0x03
、
0x06
、
0x10
(42027)0X
07E8
1
Module software
address
RW
0x01-0xE0
。
0x03
、
0x06
、
0x10
(42025)0X
07E9
1
Restore
default
parameters
RW
Write 5BB5, and the set
parameters will be restored
to the default parameters.
0x03
、
0x06
、
0x10
(42026)0x
07EA
1
Device restart
RW
Write 5BB5, the device
will restart immediately
0x03
、
0x06
、
0x10
(42100)0x
0834
1
Baud rate code
RW
The default value is
0x0003, which is 9600.
0x0000, which is 1200;
0x03
、
0x06
、
0x10