background image

 

Startup_GTF116e

-

P_r1a   Page 2 of 2

 

6.  The transmitter is fully functional as a factory calibrated airflow and temperature measurement device 

in I-P units (ft, FPM, CFM °F).  Airflow (CFM) and temperature (°F) are displayed on the LCD. If the 
transmitter is provided with the /H humidity sensor option, relative humidity (%RH) is also displayed. 

7.  If the /H humidity sensor option is provided, relative humidity (%RH) is displayed on the LCD.   

Enthalpy or dew point can also be displayed on the LCD by changing the H CONFIG parameter to 

ENTH (enthalpy) or DPT (dew point).  Press the ↑↓ arrow buttons simultaneously to enter the MAIN 

MENU.  The SETTINGS menu is displayed.  Press the ENT button to select the top of the SETTINGS 

submenu category.   Press the ↓ button until the GENERAL submenu category is visible.  Press the 
ENT button to enter the GENERAL submenu.  Press the ↓ button until the H CONFIG parameter is 

visible.  Press the ENT button and set the H CONFIG parameter to ENTH (enthalpy) or DPT (dew 

point) using the ↑↓ buttons.  Press the ENT button to save the selection.  Press the ESC button twice 

to return to normal operation. 

 

The H CONFIG setting specifies the psychrometric property assigned to analog output AO3.

 

 

If SI units are required, refer to the Operations and Maintenance Manual.

 

 

The factory default airflow output is set to actual airflow (FPM, CFM).  If standard (mass) airflow 
(SFPM, SCFM) is required, refer to the Operations and Maintenance Manual. 

8. 

Verify that the area on the hang-tag matches the actual area of the duct or opening where the probes 
are located (less any internal insulation).  If the area is different, modify the area parameter stored in 
the transmitter and use the correct area for any external conversion calculations from FPM to CFM.

   

 

Failure to use the correct area will result in volumetric airflow (CFM) measurement error and degrade 
system performance. If the area parameter must be changed, refer to the Operations and 
Maintenance Manual. 

9.  If analog output signals are used continue to step 10, otherwise skip to step 15. 
10.  The output signal type and range (4-20 mA, 0-5 VDC or 0-10VDC) of AO1, AO2 and AO3 is 

determined by the AOUT parameter.  The transmitter is factory set to 4-20mA.   

 

The 4-

20mA is “4

-

wire type” and not loop powered.  Do not apply any excitation voltage to the output 

of the transmitter.

 

11.  Verify that the transmitter is configured to match the analog input requirements of the host controller.  

Press the ESC and ↑ buttons simultaneously to display the transmitter setting for the AOUT 
parameter.  If the AOUT parameter is not correct, press the ENT button and use the ↑ and ↓ buttons 

to set AOUT.  Press the ENT button to execute and display the change.  Press the ESC button to 
return to normal operation. 

12.  The analog output signal for airflow (AO1) is linear.  The minimum scale reading (0% output) of the 

airflow signal is fixed at 0 and the full scale reading (100% output) is factory set to 5,000 FPM. 

 

Multiply the default full scale velocity (FPM )by the correct area of the measurement location to 
determine the full-scale or span (CFM ) for the B.A.S. to avoid field configuration.  EBTRON airflow 
measurement device accuracy is percent-of-reading.  Changing the full scale reading does not affect 
measurement accuracy. 

 

If custom airflow scaling or unit of measure are required, refer to the Operations and Maintenance 
Manual.  

13.  The analog output signal for temperature (AO2) is linear.  The minimum scale reading (0% output) is 

set to -20 

º

F and full scale reading (100% output) is set to 160 

º

F.    

 

If custom temperature scaling is required, refer to the Operations and Maintenance Manual.  

 

AO2 can be configured for a high/low airflow alarm or system status alarm.  Refer to the Operations 
and Maintenance Manual for more information. 

14.  The analog output signal (AO3) for the psychrometric property specified is linear.  The minimum scale 

reading (0% output) and full scale reading (100% output) is based on the psychrometric specified by 
H CONFIG.  The factory default ranges for each psychrometric property output are as follows: 

− 

Relative humidity (H CONFIG = RH): 0 to 100% 

− 

Enthalpy (H CONFIG = ENTH): 0 to 200 Btu/lb 

− 

Dew point (H CONFIG = DPT): 0 to 100 

º

 

If custom psychrometric property scaling is required, refer to the Operations and Maintenance 
Manual.

 

15.  If the LON network connection is required continue to step 16, otherwise skip to step 18. 
16.  LON transmitters are provided with a full featured LonWorks compatible interface.  No transmitter 

configuration is required. 

 

A “Service” push

-button, SW1, is provided for device commissioning.  Once the device is recognized 

commissioning can be completed by uploading the parameters from the device.

 

17.  Download the external interface file (.xif) if required by the installation software: 
 

https://ebtron.com/wp-content/uploads/software/EBTRON_116e.xif

 

 

A “Wink” LED is provided for easy device identification.

 

 

An “Activity” LED and separate transmit and receive “TX” and “RX” indicators provide visual indication 
of transmitter and communication status. The “Activity” LED flashes on for 1 second, off for 1 second 
when the card is commissioned and online. The “Activity” LED remains illuminated constantly if there 

is an error.

  

18.  Startup is complete!  If additional customization is desired, consult the 

Operation and Maintenance 

Manual

 
VERIFICATION 
Many installations require third-party airflow verification.  If the airflow measuring device is within the 
measurement uncertainty of the verification technique, EBTRON strongly recommends that no field 
adjustment correction is made.  EBTRON airflow measurement devices are factory calibrated to NIST 
traceable standards.  Field adjustment is not recommended when installed in accordance to published 
guidelines. 
If field adjustment is required, refer to the 

Operation and Maintenance Manual

 

If minimum placement guidelines cannot be achieved, installed accuracy may be compromised. 
Transmitters can be field adjusted to match a third-party measurement.  Adjusted field measurements 
typically result in comparative readings within ±3% of the third-party measurement.  Be advised that 
the third-party measurement may have uncertainties greater than or equal to ±10% and should only 
be used to adjust the airflow measurement device if the probes do not meet minimum placement 
requirements or the discrepancy is greater than the uncertainty of the third-party source. 

 