background image

 

 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 

9

 

IG_GTM

1

1

6

B_

R1

A

 

 

  

G

OLD 

S

ERIES 

GTM116-B T

RANSMITTER

 

a measurable difference! 

EBTRON 

4.2

 

GTM116

 ‐ 

ETHERNET

 

NETWORK

 

WIRING

 

CONNECTIONS

 

4.2.1

 

GTM116

 ‐ 

Connecting

 

to

 

an

 

Ethernet

 

Network

  

Connect

 

an

 

Ethernet

 

network

 

cable

 

to

 

the

 

RJ45

 

network

 

connector

 

provided

 

on

 

the

 

GTM116

 

Ethernet/Analog

 

combination

 

board

 

as

 

shown

 

in

 

Figure

 

6.

 

4.3

 

GTM116

 ‐ 

Transmitter

 

Setup

 

for

 

Ethernet

 

Network

 

Operation

 

The

 

user

 

can

 

manually

 

select

 

network

 

protocol

 

(BACnet/IP

 

or

 

BACnet

 

Ethernet

 ‐ 

MODBUS

 

TCP

 

is

 

always

 

enabled),

 

IP

 

address

 

and

 

device

 

instance

 

number,

 

or

 

can

 

set

 

the

 

GTM116

 

to

 

automatically

 

configure

 

itself

 

when

 

used

 

on

 

a

 

network/segment

 

with

 

a

 

DHCP

 

server.

 

By

 

default,

 

the

 

DHCP

 

setting

 

is

 

OFF

 

(*DHCP=OFF)

 

for

 

manual

 

device

 

configuration,

 

with

 

BACnet

 

IP

 

protocol

 

(BAC

 

MODE=IP),

 

a

 

static

 

IP

 

address

 

of

 

10.0.0.100,

 

a

 

subnet

 

mask

 

of

 

255.255.255.0,

 

and

 

with

 

gateway

 

set

 

for

 

10.0.0.10.

 

These

 

values

 

can

 

be

 

changed

 

within

 

the

 

NETWORK

 

sub

 

menu

 

as

 

described

 

below.

 

When

 

IP

 

configuration

 

is

 

complete,

 

confirm

 

communications

 

locally

 

by

 

“pinging"

 

the

 

assigned

 

GTM116

 

IP

 

address

 

and

 

observing

 

5

 

rapid

 

blinks

 

of

 

the

 

ACTIVITY

 

LED

 

(Figure

 

6).

 

4.3.1

 

GTM116

 ‐ 

Selecting

 

Static

 

or

 

Dynamic

 

IP

 

Settings

 

For

 

automated

 

device

 

configuration

 

on

 

a

 

network/segment

 

with

 

a

 

properly

 

operating

 

DHCP

 

server,

 

go

 

to

 

the

 

NETWORK

 

Menu

 

settings,

 

set

 

*DHCP=ON,

 

set

 

*BAC

 

MODE=

 

for

 

BACnet/IP

 

(factory

 

default)

 

or

 

BACnet

 

Ethernet

 

operation,

 

and

 

set

 

*DI=

 

device

 

instance

 

number

 

(factory

 

default=2)

 

as

 

described

 

below.

 

No

 

additional

 

configuration

 

is

 

required.

 

For

 

manual

 

device

 

configuration

 

of

 

the

 

GTM116,

 

set

 

NETWORK

 

menu

 

item

 

*DHCP=OFF

 

(factory

 

default).

 

When

 

manually

 

changing

 

IP

 

settings

 

(*DHCP=OFF),

 

the

 

display

 

will

 

blink

 

the

 

3

digit

 

address

 

segment

 

that

 

is

 

under

 

change.

 

Change

 

the

 

blinking

 

segment

 

by

 

pressing

 

the

 

UP

 

or

 

DOWN

 

buttons

 

to

 

arrive

 

at

 

the

 

desired

 

segment

 

setting.

 

Depress

 

the

 

ENTER

 

key

 

to

 

set

 

this

 

segment

 

and

 

to

 

move

 

the

 

blinking

 

cursor

 

to

 

the

 

next

 

(right)

 

segment.

 

Repeat

 

this

 

until

 

the

 

last

 

segment

 

has

 

been

 

selected,

 

and

 

then

 

depress

 

ENTER

 

to

 

store

 

the

 

new

 

address

 

setting.

 

4.3.2

 

GTM116

 ‐ 

Setting

 

Ethernet

 

Transmitter

 

IP

 

Address

 

The

 

GTM116

 

is

 

factory

 

set

 

with

 

an

 

IP

 

address

 

of

 

10.0.0.100.

 

Each

 

transmitter

 

must

 

be

 

assigned

 

a

 

unique

 

address

 

on

 

the

 

network/segment

 

it

 

is

 

connected

 

to.

 

To

 

change

 

the

 

IP

 

address

 

in

 

the

 

NETWORK

 

menu,

 

navigate

 

to

 

the

 

*IP=10.0.0

 

item,

 

and

 

set

 

segments

 

as

 

previously

 

described.

 

(See

 

note

 

above

 

regarding

 

*DHCP=OFF).

 

4.3.3

 

GTM116

 ‐ 

Setting

 

Subnet

 

Mask

 

To

 

change

 

this

 

value,

 

navigate

 

to

 

the

 

*MASK=255.2...

 

NETWORK

 

menu

 

item,

 

and

 

set

 

new

 

segment

 

values

 

as

 

previously

 

described.

 

(See

 

note

 

above

 

regarding

 

*DHCP=OFF).

 

4.3.4

 

GTM116

 ‐ 

Setting

 

Gateway

 

IP

 

To

 

change

 

this

 

value,

 

navigate

 

to

 

the

 

*GATE=10.0.0...

 

NETWORK

 

menu

 

item,

 

and

 

set

 

new

 

segment

 

values

 

as

 

previously

 

described.

 

(See

 

note

 

above

 

regarding

 

*DHCP=OFF).

 

4.3.5

 

GTM116

 ‐ 

Setting

 

BACnet

 

Protocol

 

Mode

 

The

 

GTM116

 

is

 

factory

 

set

 

with

 

*BAC

 

MODE=IP

 

for

 

BACnet

 

IP

 

protocol

 

operation.

 

This

 

NETWORK

 

menu

 

item

 

can

 

be

 

changed

 

to

 

*BAC

 

MODE=ETH

 

for

 

BACnet

 

Ethernet

 

protocol.

  

Tables

 

3,

 

4

 

and

 

5

 

provide

 

details

 

of

 

TCP/IP,

 

BACnet

 

Objects

 

and

 

Modbus

 

Register

 

Maps

 

respectively.

 

Note

 

that

 

Modbus

 

IP

 

is

 

always

 

enabled

 

regardless

 

of

 

*BAC

 

MODE

 

setting.

 

NOTE:

 

For

 

BACnet

 

IP

 

operation,

 

use

 

port

 

47808.

 

For

 

Modbus

 

TCP

 

operation,

 

use

 

port

 

502.

 

Modbus

 

IP

 

is

 

always

 

enabled

 

regardless

 

of

 

the

 

*BAC

 

MODE

 

setting.

 

4.3.6

 

GTM116

 ‐ 

Setting

 

Device

 

Instance

 

Number

 

The

 

GTM116

 

is

 

factory

 

set

 

with

 

a

 

Device

 

Instance

 

Number

 

of

 

2

 

(*DI=2).

 

The

 

Device

 

Instance

 

Number

 

can

 

be

 

set

 

to

 

any

 

value

 

between

 

0

 

and

 

4194302

 

as

 

shown

 

in

 

Appendix

 

A.

 

The

 

Device

 

Instance

 

Number

 

can

 

also

 

be

 

changed

 

by

 

writing

 

to

 

the

 

Device

 

Object's

 

Object

 

Identifier

 

Property

 

over

 

the

 

network.

 

Summary of Contents for Advantage III Gold Series

Page 1: ...rflow Sensors Combination Ethernet Network Output and Dual Analog Output Document Name IG_GTM116 B_R1B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse...

Page 2: ...TER START UP INITIALIZATION AND SETUP MENUS 11 5 1 Changing the System of Units IP or SI Units 11 5 2 GTM116 Transmitter Calibration 11 5 3 GTM116 LCD Display Notifications 11 5 4 Factory Default Menu...

Page 3: ...re 4 Type B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTM116 Combination Analog Ethernet Transmitter Interior Detail 8 List of Tables Table 1 GTM116 Power Transformer S...

Page 4: ...in 50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all conn...

Page 5: ...ed LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable recept...

Page 6: ...VA Req 1 12 5 14 2 13 6 15 3 13 7 15 4 14 8 16 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input terminal labeled POWER on the upper right hand side o...

Page 7: ...de a drip loop at the transmitter if there will be the potential for water runoff or condensation along the bleed sensor cable s Bleed sensor cable plugs are keyed as shown below Line up plug with rec...

Page 8: ...o wire the analog outputs slide the cover plate up and off of the enclosure Ensure that the power switch is in the OFF position Connect signal wires for airflow rate or equivalent differential pressur...

Page 9: ...digit address segment that is under change Change the blinking segment by pressing the UP or DOWN buttons to arrive at the desired segment setting Depress the ENTER key to set this segment and to mov...

Page 10: ...nsert 1 Flow 30019 30020 Insert 4 Flow 4 30021 30028 float F Temperature Traverse 20 to 160 30021 30022 Insert 1 Temp 30027 30028 Insert 16 Temp 4 30029 30030 float Sq Ft Area 0 to 100 4 300202 word F...

Page 11: ...s are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 5 IP System of Units Description SI System of Units Descrip...

Page 12: ...set factor 0 000 0 000 AO2 SGNL Output 2 signal voltage or mA temperature or alarm mA see alarms mA see alarms AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70...

Page 13: ...desired the output can be set to provide standard airflow measurement units displayed as SCFM and SFPM which provides measurements that are corrected to standard conditions 5 5 4 Output Scaling EBTRON...

Page 14: ...and AO2 alarm output indications User can select either or both of the two Average Alarms or the Trouble Alarm 5 6 5 Low Alarm LO ALRM ON The Low Alarm is activated when the average airflow falls belo...

Page 15: ...ntrol system To set a fixed output signal for airflow and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain...

Page 16: ...odbus networks or via EB Link Reader Airflow and temperature of individual sensors can be read across BACnet or Modbus networks or downloaded directly to an EB Link Reader if the infra red EB Link opt...

Page 17: ...cters for blank or unwanted text EXT CABLE 0 SET EXT CABLE EXT CABLE 0 LCD TRBL ON Set measurement mode to AIRFLOW MEAS PRESS LCD DSPL BOTH SETUP Instruction text USE AND ENT then NAME _ GENERAL SET O...

Page 18: ...ate this setting is fixed and cannot be modified AO1 ASGN iWG AO1 UM FIXED The text AO1 UM FIXED flashes to indicate that this setting is fixed and cannot be modified ANALOG OUT AO1 ASGN FLOW SET AO1...

Page 19: ...ve to right and ESC to move to left Set network device instance number Set network protocol type Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and E...

Page 20: ...low alarm setpoint Units based on ALARM UM DELAY 2 MIN SET DELAY DELAY 2 MIN Enter alarm delay RESET AUTO SET RESET RESET AUTO Set alarm RESET AUTO will clear once the alarm is not active MANUAL requi...

Page 21: ...Adjust Wizard will now be engaged as outlined in the following steps The GAIN and OFF values will be updated and PRESS ADJ ON will be set if the wizard is successfully completed OF PRESS 2 OUT2 TEST...

Page 22: ...RESET ADJ NO RESET ALL NO Sets security level to MED In this mode a user defined code is specified In the event of loss of code contact EBTRON for a unique code for this transmitter to unlock and rese...

Page 23: ...te 2 L2 L1 POWER 24VAC IN OUT 1 AIRFLOW PRESSURE OUTPUT SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS INTERFACE OUT 2 can be set as an analog Temperature Alarm or Trouble o...

Page 24: ...1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com IG_GTM116 B_R1A GOLD SERIES GTM116 B TRANSMITTER a measurable difference EBTRON a measurable differen...

Reviews: