ebm-papst W6E630-GN01-01 Operating Instructions Manual Download Page 2

Operating instructions

W6E630-GN01-01

Translation of the original operating instructions

CAUTION
Electrical load on the capacitor after device is switched off

Electric shock, risk of injury
→ Discharge the capacitors before working on the device.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ Insert the brought-out thermal overload protector into the

control circuit so that the cooled off motor does not switch on
independently after a fault.

1.5 Safety and protective functions

DANGER
Guard missing and guard not functioning

Without a guard there is a risk of serious injury, for instance
when reaching into the device during operation. Loose parts or
items of clothing could be drawn in.
→ The device is a built-in component. As the operator, you are

responsible for ensuring that the device is secured
adequately.# Operate the device only with a fixed protective
device and guard grille.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

WARNING
Damage to guard grille, ejected parts

The guard grille is not designed to bear heavy loads. Parts
lying on or falling through the guard grille can be ejected by a
running fan.
→ Do not step on the guard grille or subject it to heavy loads.
→ Do not place any objects on the guard grille. In the area

around the fan, there must be sufficient space for people to
pass by the fan.

1.6 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, dangling items of clothing, jewellery and similar items
can become entangled and be pulled into the device. Risk of
injury.
→ Do not wear any loose-fitting or dangling clothing or jewellery

while working on rotating parts.

→ Protect long hair with a cap.

1.7 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.8 Hot surface

CAUTION
High temperature at the motor housing

Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is

provided.

1.9 Transport

NOTE
Transport of device

→ Transport the device in its original packaging only.
→ Secure the device so that it does not slip, e.g. by using a

clamping strap.

1.10 Storage

;

Store the device, partially or fully assembled, in the original
packaging in a clean, dry and weatherproof place free of vibrations.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and longest possible service
life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.

;

Please make sure that all screwed cable glands are fitted with
dummy plugs.

Item no. 10125-5-9970 · ENG · Revision 98149 · Release 2020-10-06 · Page 2 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W6E630-GN01-01

Page 1: ... specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy...

Page 2: ...the fan there must be sufficient space for people to pass by the fan 1 6 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and sim...

Page 3: ...s Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation O...

Page 4: ...e the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10125 5 9970 ENG Revision 98149 Release 2020 10 06 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...teel blank sprayed with PP plastic Material of wall ring Sheet steel pre galvanised and coated in black plastic RAL 9005 Material of guard grille Steel coated in black plastic RAL9005 Number of blades 5 Direction of air flow V Direction of rotation Counter clockwise seen on rotor Type of protection IP54 Insulation class F Humidity F environmental protection class H H2 Mounting position Shaft horiz...

Page 6: ...tions to the device Replacing the terminal box is not permitted NOTE Motor capacitor The product is equipped with a motor capacitor with safety protection class P0 S0 according to EN 60252 1 Take this into consideration when fitting it to the end product on the basis of applicable regulations CAUTION Possibility of damage to the device Serious damage may result if the device slips during assembly ...

Page 7: ...lowing installation in the end device 4 2 4 Frequency inverter Please use a frequency converter only after consultation with ebm papst For operation with frequency converters fit sinusoidal filters that work on all poles phase phase and phase earth between the frequency converter and the motor During operation with frequency converters an all pole sine filter protects the motor against high voltag...

Page 8: ...n switch When working on the device the system machine in which the device is installed must be secured so as to prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil The motors are equipped with thermal overload protectors to protect the devices Check to...

Page 9: ...s 4 4 Connection screen L U1 blue Z brown N U2 black PE green yellow TOP grey Item no 10125 5 9970 ENG Revision 98149 Release 2020 10 06 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 10: ...ibrations can result from improper handling imbalance resulting from damage during transport or component induced or structural resonances When putting the fan into service determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation a...

Page 11: ...ater jet or high pressure cleaner Do not use any acid alkali or solvent basedcleaning agents Do not use any pointed or sharp edged objects for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rotating parts are not permissible Operate the fan for 2 hours at ...

Page 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 5 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...

Reviews: