background image

Operating instructions

W4E315-CA05-51

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND INFORMATION

1

1. SAFETY REGULATIONS AND INFORMATION

Read these operating instructions carefully before starting work on the
device. Observe the following warnings to prevent malfunctions or
danger to persons.
These operating instructions are to be regarded as part of the device.
The device is only to be sold or passed on together with the operating
instructions.
These operating instructions may be duplicated and distributed to inform
about potential dangers and their prevention.

1.1 Hazard levels for warnings

1

1.1 Hazard levels for warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which will result in
death or serious injury if the specified actions are not taken.
Compliance with the instructions is imperative.

WARNING

Indicates a potentially hazardous situation which can result in
death or serious injury if the specified actions are not taken.
Exercise extreme caution while working.

CAUTION

Indicates a potentially hazardous situation which can result in
minor or moderate injury or damage to property if the specified
actions are not taken.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualifications

1

1.2 Staff qualifications

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by suitably qualified, trained and
authorized technical staff.
Only authorized specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

The safety hazards associated with the device must be assessed again
following installation in the final product.
The locally applicable industrial safety regulations are always to be
observed when working on the device.
Keep the workplace clean and tidy. Untidiness in the work area
increases the risk of accidents.
Note the following when working on the device:

;

Do not perform any modifications, additions or conversions on the
device without the approval of ebm-papst.

1.4 Voltage

1

1.4 Voltage

;

Check the device's electrical equipment at regular intervals; see
Chapter 5.2 Safety inspection.

;

Replace loose connections and defective cables immediately.

DANGER
Electrically charged device

Risk of electric shock
→ When working on an electrically charged device, stand on a

rubber mat.

2

1.5 Safety and protective features

2

1.6 Mechanical movement

2

1.7 Emissions

2

1.8 Hot surface

2

1.9 Transport

2

1.10 Storage

3

2. INTENDED USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Technical description

5

3.4 Mounting data

5

3.5 Transport and storage conditions

6

4. CONNECTION AND STARTUP

6

4.1 Mechanical connection

6

4.2 Electrical connection

7

4.3 Connecting the cables

8

4.4 Connection diagram

9

4.5 Checking connections

9

4.6 Switching on the device

9

4.7 Switching off the device

9

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

10

5.1 Cleaning

10

5.2 Safety inspection

10

5.3 Disposal

Item no. 14447-5-9970 · ENU · Change 254192 · Approved 2022-03-02 · Page 1 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W4E315-CA05-51

Page 1: ... and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applica...

Page 2: ...Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry while working on rotating parts Protect long hair with a cap 1 7 Emissions WARNING Depending on t...

Page 3: ...ld be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws coming...

Page 4: ...uct drawing All dimensions in mm 1 Direction of air flow V 2 Cable silicone 4G 0 5 mm 4x crimped splices Item no 14447 5 9970 ENU Change 254192 Approved 2022 03 02 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...ble Lateral Protection class I with customer connection of protective earth Conformity with standards EN 60335 1 NM Comment on CE Commissioning not permitted in the European Economic Area Approval UL 507 Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality m...

Page 6: ...sconnection switch When working on the fan secure the system machine in which the fan is installed so as to prevent it from being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole d...

Page 7: ...ect the cables according to your application When doing so observe Chapter 4 4 Connection diagram 4 3 1 Cable routing Water must be prevented from reaching the cable exit along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cabl...

Page 8: ...uctions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 14447 5 9970 ENU Change 254192 Approved 2022 03 02 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ... MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION Electric charge on capacitor after device is switched off Electric ...

Page 10: ...ing the protective earth terminal Visual inspection At least every 6 months Fasten Insulation of cables for damage Visual inspection At least every 6 months Replace cables Condensation drainage holes for clogging where necessary Visual inspection At least every 6 months Open holes Welds for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At ...

Page 11: ...materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 14447 5 9970 ENU Change 254192 ...

Reviews: