3.2 Nominal data

Motor

M4E068-CF

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

ml

ml

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

1320

1500

Power consumption / W

72

90

Current draw / A

0.32

0.4

Capacitor / µF

2

2

Capacitor voltage / VDB

400

400

Capacitor standard

S0 (CE)

S0 (CE)

Max. back pressure / Pa

45

55

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

50

50

Starting current / A

0.6

0.57

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

2.95 kg

Size

300 mm

Motor size

68

Rotor surface

Painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Fan housing material

PP plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Any

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing with low-temperature lubricant

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1; CE

Approval

EAC; CCC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 70 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.6 Accessories

3.6.1 AxiCool heating tape

A heating tape that can be installed in the fan housing is available for the
AxiCool fans. To prevent ice formation, ebm-papst recommends the use
of a heating tape for all applications below 0 °C. The heating tape
designed for the AxiCool fan housing is available from ebm-papst under
the following item numbers.

Fan size

Item no.

300 mm

00300-2-7680

350 mm

00350-2-7680

450 mm

00450-2-7680

During assembly, comply with the installation instructions included with
each ebm-papst heating tape.
ebm-papst assumes no liability when heating tapes from other
manufacturers are used. Note the maximum permitted temperature of
+60 ± 5 °C for the heating tape to prevent damage to the wall ring.

Item no. 12627-5-9970 · ENU · Change 202174 · Approved 2019-01-07 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W4E300-JS72-30

Page 1: ...wise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical ins...

Page 2: ...coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating dev...

Page 3: ...ing the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer...

Page 4: ...ng All dimensions in mm 1 Direction of air flow V 2 Cable PVC 4G 0 5mm 4x crimped splices 3 Mounting dimensions Item no 12627 5 9970 ENU Change 202174 Approved 2019 01 07 Page 4 10 ebm papst Mulfingen...

Page 5: ...Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may change during the production period This has no effect on s...

Page 6: ...s that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection data If the motor run capacitor was not instal...

Page 7: ...etrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop wherever...

Page 8: ...ctions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 12627 5 9970 ENU Change 202174 Approved 2019 01 07 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen...

Page 9: ...your device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltag...

Page 10: ...serve the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also...

Reviews: