ebm-papst W4D315-CS10-30 Operating Instructions Manual Download Page 6

Operating instructions

W4D315-CS10-30

Translation of the original operating instructions

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the device
from the packaging

Blades can be bent
→ Carefully remove the device from its packaging, only

touching the wall ring. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to device from vibration

Bearing damage, reduced service life
→ Forces or impermissibly high vibration levels must not be

transmitted to the fan from system components. #If the fan is
connected to air ducts, it should isolated from vibrations, for
example using compensators or similar elements. #Fasten
the fan to the substructure without distorting it.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

CAUTION
Possibility of damage to the device

Serious damage may result if the device slips during assembly.
→ Keep the device fixed in position at the installation location

until all attachment screws have been tightened.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check that the data on the type plate match the connection data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Protective earth contact resistance as per EN 60335

Compliance with the resistance specifications as per EN 60335 for the
protective earth connection circuit must be verified in the application.
Depending on the installation situation, it may be necessary to connect
an additional protective earth conductor by way of the extra protective
earth terminal provided on the device.

4.2.2 Voltage control

With open loop speed control using transformers or electronic
voltage regulators (e.g. phase angle control), excessive current
may occur.
In addition, noises can occur with phase angle control
depending on the mounting situation.

4.2.3 Frequency inverter

Please use a frequency converter only after consultation with ebm-papst.
When a frequency converter is used for speed adjustment, the
maximum safe operating speed (see 3.2 Nominal data) may not be
exceeded.

For operation with frequency converters, fit sinusoidal filters that
work on all poles (phase-phase and phase-earth) between the
frequency converter and the motor.
During operation with frequency converters, an all-pole sine
filter protects the motor against high-voltage transients that can
destroy the winding insulation system, and against harmful
bearing currents.

Heating of the motor due to use of a frequency converter must be
checked in the application by the customer.

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

Item no. 14282-5-9970 · ENG · Revision 89188 · Release 2016-04-18 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W4D315-CS10-30

Page 1: ...d trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rul...

Page 2: ...s have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk of injury Do not wear any l...

Page 3: ...ing instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resona...

Page 4: ...All measures have the unit mm 1 Direction of air flow V 2 Connection line silicone 4G 0 5 mm 4x lead tips crimped Item no 14282 5 9970 ENG Revision 89188 Release 2016 04 18 Page 4 10 ebm papst Mulfin...

Page 5: ...n class I if protective earth is connected by customer Product conforming to standard EN 60335 1 motor does not have factory installed overheating protection For cyclic speed loads note that the rotat...

Page 6: ...e disconnecting switch 4 2 1 Prerequisites Check that the data on the type plate match the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of...

Page 7: ...in upright position The cables must always be routed downwards 4 3 2 Motor protection WARNING Device without overheating protection The device is delivered without any automatically functioning overhe...

Page 8: ...se motor Y Star connection 1 Anti clockwise operation L1 V1 blue L2 U1 black L3 W1 brown 2 Clockwise operation L1 U1 black L2 V1 blue L3 W1 brown PE green yellow Item no 14282 5 9970 ENG Revision 8918...

Page 9: ...e supply line When disconnecting be sure to disconnect the earth wire connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the devic...

Page 10: ...nts Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal stand...

Reviews: