ebm-papst W3G990-DZ02-35 Operating Instructions Manual Download Page 5

Operating instructions

W3G990-DZ02-35

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-NA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

960

Power input / W

2580

Current draw / A

4.0

Max. back pressure / Pa

180

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

70

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Measurement category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

54.4

32.2

36.2

Efficiency grade N

58.2

36

40

Power input P

ed

/ kW

2.54

Air flow q

v

/ m³/h

24185

Pressure increase total p

sf

/ Pa

194

Speed n / min

-1

965

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

60 kg

Size

990 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium, coated in black

Material of blades

Aluminium sheet insert (coated in black),
sprayed with PP plastic

Material of mounting
ring

Steel, galvanised and coated in black
plastic (RAL9005)

Material of wall ring

Sheet steel, pre-galvanised and coated in
black plastic (RAL 9005)

Number of blades

5

Blade angle

-5°

Direction of air flow

"A"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F5

Mounting position

Shaft horizontal or rotor on top; rotor on
bottom on request

Condensate discharge
holes

On the stator side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

C22.2 Nr.77 + CAN/CSA-E60730-1;
EAC; UL 1004-7 + 60730

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

Item no. 51477-5-9970 · ENG · Revision 82871 · Release 2015-05-12 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W3G990-DZ02-35

Page 1: ...y out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installe...

Page 2: ...NGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long...

Page 3: ...Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical eq...

Page 4: ...the unit mm 1 Direction of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 51477 5 9970 ENG Revision 82871 Release 2015 05 12 Page 4 1...

Page 5: ...on rotor Type of protection IP 54 Insulation class F Humidity class F5 Mounting position Shaft horizontal or rotor on top rotor on bottom on request Condensate discharge holes On the stator side Oper...

Page 6: ...dily harm e g back injuries are possible Two people should remove the device out of its packaging together Check the device for transport damage Damaged devices must no longer be installed Install the...

Page 7: ...ss section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG...

Page 8: ...ble routing No water may penetrate along the cable in the direction of the cable gland Fans installed lying flat Make sure that the cable is routed in the form of a loop water trap Fig 3 Fan installed...

Page 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Page 10: ...he fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the de...

Page 11: ...ly Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor windi...

Page 12: ...or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At l...

Reviews: