ebm-papst W3G990-DW30-55 Operating Instructions Manual Download Page 5

Operating instructions

W3G990-DW30-55

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-FF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

ml

State

prelim.

Speed / min

-1

820

Power input / W

1390

Current draw / A

6.1

Max. back pressure / Pa

70

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

47.1

31

35

Efficiency grade N

52.1

36

40

Power input P

ed

/ kW

1.63

Air flow q

v

/ m³/h

19880

Pressure increase total p

sf

/ Pa

130

Speed n / min

-1

805

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

52.7 kg

Size

990 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium, coated in black

Material of blades

Aluminium sheet insert (coated in black),
sprayed with PP plastic

Material of mounting
ring

Steel, galvanised, primed and coated in
black plastic

Material of wall ring

Sheet steel, pre-galvanised and coated in
black plastic

Number of blades

5

Blade angle

-5°

Direction of air flow

"A"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F5

Mounting position

Shaft horizontal or rotor on top

Condensate discharge
holes

On the stator side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Tach output
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Output limit
- Motor current limit
- PFC, active
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

Item no. 51661-5-9970 · Revision 82539 · Release 2014-05-08 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W3G990-DW30-55

Page 1: ...l the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated...

Page 2: ...DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Lo...

Page 3: ...arly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation...

Page 4: ...ve the unit mm 1 Direction of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 51661 5 9970 Revision 82539 Release 2014 05 08 Page 4 12...

Page 5: ...ction of rotation Counter clockwise seen on rotor Type of protection IP 54 Insulation class F Humidity class F5 Mounting position Shaft horizontal or rotor on top Condensate discharge holes On the sta...

Page 6: ...rrect insulation Risk of fatal injury from electric shock Use only cables that meet the specified installation requirements for voltage current insulation material load etc Route cables such that they...

Page 7: ...typical 4 W 4 2 3 Residual current operated device Only universal type B or B RCD protective devices are permitted Like frequency inverters RCD protective devices cannot provide personal safety while...

Page 8: ...routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM co...

Page 9: ...DC disabling bridge to GND or applied voltage 0 8 VDC reset function triggers software reset after a level change to 0 8 V KL3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setti...

Page 10: ...f the protective features before switching it on Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device...

Page 11: ...gise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Page 12: ...every 6 months Retighten replace if damaged Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore holes Weld seams for crack formation Visual inspect...

Reviews: