ebm-papst W3G630-NP04-H1 Operating Instructions Manual Download Page 5

Operating instructions

W3G630-NP04-H1

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-GF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 270

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

830

Power consumption / W

410

Current draw / A

1.8

Max. back pressure / Pa

100

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

47.6

31.1

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

56.5

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

W3G630-NP04-H1

09 Power consumption P

ed

/ kW

0.38

09 Air flow q

v

/ m³/h

6785

09 Pressure increase total p

sf

/

Pa

88

10 Speed (rpm) n / min

-1

830

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Size

630 mm

Motor size

84

Rotor surface

Painted black

Terminal box material

PP plastic

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

PP plastic

Fan housing material

Sheet steel, galvanized and coated with
black plastic (RAL 9005)

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Blade pitch

Airflow direction

V

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing; (sealed)

Technical features

- Output 10 VDC, max. 10 mA
- Operation and alarm display
- Alarm relay
- Integrated PID controller
- Power limiter
- Motor current limitation
- PFC, active
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

EAC; CSA C22.2 No. 77 + CAN/CSA-
E60730-1; UL 1004-7 + 60730-1

Comment

Conformity with standard EN 60335-1 on
request

Item no. 57391-5-9970 · ENU · Change 212910 · Approved 2021-03-30 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W3G630-NP04-H1

Page 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated w...

Page 2: ...ion appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC co...

Page 3: ...n particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation op...

Page 4: ...Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 3 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use must be made of seal provided Cable diameter min 4 mm max 7 mm tigh...

Page 5: ...motor impeller combination in a standardized measurement setup 3 4 Technical description Size 630 mm Motor size 84 Rotor surface Painted black Terminal box material PP plastic Electronics housing mat...

Page 6: ...hazard when removing device from packaging Blades can bend Carefully remove the device from its packaging by the fan housing Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CA...

Page 7: ...rovided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Reactive currents Because of the EMC filter integrated for co...

Page 8: ...er is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop wherever possible If this is not possible a...

Page 9: ...ontact common connection contact rating 250 VAC 2 A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 8 GND Reference ground for control interface SELV...

Page 10: ...witching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power sup...

Page 11: ...ning agents used If severe corrosion is visible on load bearing or rotating parts switch off the device immediately and replace it Repair of load bearing or rotating parts is not permitted Operate the...

Page 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are...

Reviews: