Operating instructions

W3G630-KE55-21

Translation of the original operating instructions

All dimensions in mm.

1

Installation position: Shaft horizontal (install support struts only in X-position as illustrated) or rotor on bottom

2

For horizontal shaft installation position, the cable exit must be at the bottom right.

Item no. 55308-5-9970 · ENU · Change 205336 · Approved 2021-03-15 · Page 5 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W3G630-KE55-21

Page 1: ...install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be ass...

Page 2: ...g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or...

Page 3: ...device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the opera...

Page 4: ...mm 1 Airflow direction V 2 Cable PVC AWG18 5x crimped ferrules 3 Cable PVC AWG22 5x crimped ferrules 4 Mounting holes for FlowGrid Item no 55308 5 9970 ENU Change 205336 Approved 2021 03 15 Page 4 13...

Page 5: ...ort struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 55308 5 9970 ENU Change 205336 Approved...

Page 6: ...a standardized measurement setup 3 4 Technical description Weight 18 75 kg Size 630 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade ma...

Page 7: ...om ebm papst under the following item number Size Item no 630 mm 00630 2 7680 During assembly comply with the installation instructions included with each ebm papst heating tape ebm papst assumes no l...

Page 8: ...the tightening torque recommended by ebm papst must be checked in the application concerned 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth firs...

Page 9: ...ly has basic insulation for TN TT systems or functional insulation for phase conductor grounded networks with respect to the supply voltage and not double insulation like the rest of the interface cor...

Page 10: ...elay floating status contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 2 8 0 10V yellow Analog input...

Page 11: ...and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies must be determined in the course of fan...

Page 12: ...ocate and rectify cause of error release restart lockout if necessary Ambient temperature too high Reduce the ambient temperature Reset by reducing control input to 0 Impermissible point of operation...

Page 13: ...the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be...