Operating instructions

W3G630-DQ37-35

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

PE

-

PE

Protective earth terminal

KL1

1, 2

N, L

Power supply 50/60 Hz

KL2

1

NC

Floating status contact, break for failure

KL2

2

COM

Floating status contact, changeover contact, common connection
(2 A, max. 250 VAC, min. 10 mA, AC1)

KL2

3

NO

Floating status contact, make for failure

KL3

1

OUT

Analog output, 0-10 VDC, max. 3 mA, SELV
output of current motor modulation level:
1 V corresponds to 10% modulation level.
10 V corresponds to 100% modulation level.

KL3

2, 8

GND

Reference ground for control interface, SELV

KL3

3, 7

0-10 V

Control/current sensor value input 0-10 VDC, impedance 100 kΩ, use only as alternative to 4-20 mA input,
SELV

KL3

4

+10 V

Voltage output 10 VDC (+/- 3%), max. 10 mA,
power supply for ext. devices (e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA
power supply for ext. devices (e.g. sensors), SELV

KL3

6

4-20 mA

Control/current sensor value input 4-20 mA, impedance 100 Ω, use only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for MODBUS, RSB

KL3

10, 12

RSA

RS485 interface for MODBUS, RSA

Item no. 52150-5-9970 · ENU · Change 88834 · Approved 2016-04-29 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

E-mail: [email protected]  

Summary of Contents for W3G630-DQ37-35

Page 1: ...tably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Ba...

Page 2: ...he impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause b...

Page 3: ...device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sust...

Page 4: ...ction of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 52150 5 9970 ENU Change 88834 Approved 2016 04 29 Page 4 11 ebm papst Mulfinge...

Page 5: ...rement setup 3 4 Technical description Weight 22 5 kg Fan size 630 mm Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted painted sheet...

Page 6: ...sulation Risk of fatal injury from electric shock Use only cables that meet the specified installation regulations for voltage current insulation material capacity etc Route cables so that they cannot...

Page 7: ...operating the device When the device s power supply is switched on pulsed charging currents from the capacitors in the integrated EMC filter can lead to the residual current devices tripping without d...

Page 8: ...3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Control current sensor value input 0 10 VDC impedance 100 k use only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage output...

Page 9: ...rror An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line vol...

Page 10: ...fter that period contact ebm papst Adjust maintenance intervals to the level of dust exposure 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping curre...

Page 11: ...ls Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be dis...

Reviews: