ebm-papst W3G560-DP68-35 Operating Instructions Manual Download Page 8

Operating instructions

W3G560-DP68-35

Translation of the original operating instructions

Fig. 2: Connecting wires to terminals

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

Fans installed upright

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 3: Cable routing for fans installed upright.

4.4 Factory settings

Factory settings made for the device by ebm-papst.

Mode parameter set 1

PWM control

Mode parameter set 2

PWM control

Fan/device address

01

Max. PWM / %

100

Min. PWM / %

8,0

Save set value to
EEPROM

No

Set value requirement

Analog (linear)

Direction of action
parameter set 1

Positive (heating)

Direction of action
parameter set 2

Positive (heating)

Item no. 52189-5-9970 · ENU · Change 88834 · Approved 2016-04-29 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

E-mail: [email protected]  

Summary of Contents for W3G560-DP68-35

Page 1: ...ably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Bas...

Page 2: ...against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan...

Page 3: ...ing ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sustaining or life suppor...

Page 4: ...tion of air flow A 2 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 3 Tightening torque 3 5 0 5 Nm Item no 52189 5 9970 ENU Change 88834 Approved 2016 04 29 Page 4 12 ebm papst Mulfing...

Page 5: ...setup 3 4 Technical description Weight 18 7 kg Fan size 560 mm Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Sheet aluminum insert painted bl...

Page 6: ...ury from electric shock Use only cables that meet the specified installation regulations for voltage current insulation material capacity etc Route cables so that they cannot be touched by any rotatin...

Page 7: ...vices tripping without delay We recommend the use of residual current circuit breakers with a trip threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 4 Locked rotor protecti...

Page 8: ...installed upright 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 8...

Page 9: ...3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Control current sensor value input 0 10 VDC impedance 100 k use only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage output...

Page 10: ...ES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety feature description function Rotor position detection...

Page 11: ...signed for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adjust maintenance intervals to the level of dust exposure 6 2 Safety inspection NOTE...

Page 12: ...s metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magn...

Reviews: