background image

Operating instructions

W3G300-ZC05-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G055-CF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1400

Power consumption / W

70

Current draw / A

0.7

Max. back pressure / Pa

105

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Size

300 mm

Motor size

55

Rotor surface

Thick-film passivated

Terminal box material

PP plastic

Impeller material

PP plastic

Fan housing material

PP plastic

Number of blades

5

Airflow direction

V

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Any

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 1.1 mA
- Tach output
- Power limiter
- Motor current limitation
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Overvoltage detection
- Thermal overload protection for
electronics/motor
- Line undervoltage detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Electronic motor protection

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60034-1; EN 60204-1; EN 60335-1;
CE

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; EAC; UL 1004-7 + 60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.4 Mounting data

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.6 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC circuit feedback

According to EN 61000-3-2/3

EMC interference
emission

According to EN 61000-6-3 (household
environment)

Item no. 57962-5-9970 · ENU · Change 231535 · Approved 2021-05-05 · Page 7 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W3G300-ZC05-01

Page 1: ...orized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observe...

Page 2: ...C compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the de...

Page 3: ... be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws coming l...

Page 4: ... 1 3 0 2 Nm Accessory part Guard grill 30070 2 4039 with oval head screw 60080 7 6201 4x can be fitted on the intake side Not included in scope of delivery The installation of accessories may change the air performance and noise values Item no 57962 5 9970 ENU Change 231535 Approved 2021 05 05 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938...

Page 5: ...ll dimensions in mm 1 Guard grill 30070 2 4039 2 Oval head screw 60080 7 6201 4x Item no 57962 5 9970 ENU Change 231535 Approved 2021 05 05 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 6: ...take side mounting on suction nozzle The Ø6 5 mm holes must be pierced from the underside with a mandrel or similar tool We recommend using M6 cheese head screws with hexagon socket DIN 912 DIN EN ISO 4762 for fastening 3 outlet side mounting on flange Item no 57962 5 9970 ENU Change 231535 Approved 2021 05 05 Page 6 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 8...

Page 7: ...4 7 60730 1 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality ma...

Page 8: ...or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection data Before connecting the device make sure the power supply matches...

Page 9: ...nal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly presen...

Page 10: ...ve earth 1 GND blue GND connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10 V max 1 1 mA red Voltage output 10 VDC 1 1 mA electrically isolated short circuit proof 4 Tacho white Tach output open collector 1 pulse per revolution electrically isolated Item no 57962 5 9970 ENU Change 231535 Approved 2021 05 05 Page 10 13 ebm papst Mulfingen GmbH ...

Page 11: ...upply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the e...

Page 12: ...hat period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of th...

Page 13: ...inum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electric...

Reviews: