Operating instructions

W2D250-GA04-09

Translation of the original operating instructions

4.2.2 Voltage control

NOTE

Current overshoots may occur if speed control is implemented
by transformers or electronic voltage regulators (e.g. phase
control). Depending on the type of installation of the device,
noise and vibration may also occur in the case of phase
control. Vibration can lead to bearing damage and thus
premature failure.

Heating-up of the motor when using voltage control must be checked by
the customer following installation in the end device.

4.2.3 Variable frequency drive

Please use a variable frequency drive only after consultation with ebm-
papst.

For operation with variable frequency drives, install sinusoidal
filters that work on all poles (phase-phase and phase-ground)
between the drive and the motor.
During operation with variable frequency drives, an all-pole
sine filter protects the motor against high-voltage transients that
can destroy the coil insulation system, and against harmful
bearing currents.

Heating-up of the motor when using a variable frequency drive must be
checked by the customer following installation in the end device.

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.5 Connection diagram.

4.3.1 Cable routing

Water must be prevented from reaching the cable exit along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Fig. 1: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed upright

Fig. 2: Cable routing for fans installed upright. The cables must always
be routed downward.

4.3.2 Motor protection

WARNING
Device has no overheating protection

The device is supplied without any automatic overheating
protection. The device can become hot and catch fire.
→ For the version without thermal overload protector, also

install a suitable motor protection switch.

4.4 Connection of the Hall IC

The device has external leads.

;

Connect the cables according to your application. When doing so,
observe Chapter 4.5 Connection diagram.

Item no. 10425-5-9970 · ENU · Change 236565 · Approved 2021-07-16 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W2D250-GA04-09

Page 1: ...ned and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1...

Page 2: ...ndstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or da...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...r flow V 2 Cable PVC 4x crimped splices 3 Connection for speed monitoring brought out AWG24 300V Hall generator motor and Hall sensor wires not stripped Item no 10425 5 9970 ENU Change 236565 Approved...

Page 5: ...eight 3 02 kg Size 250 mm Motor size 68 Rotor surface Painted black Impeller material Sheet steel hot dip galvanized Fan housing material Sheet steel pre galvanized and coated with black plastic Guard...

Page 6: ...on Risk of fatal injury from electric shock Use only cables that meet the specified installation regulations for voltage current insulation material capacity etc Route cables so that they cannot be to...

Page 7: ...earth Connect the cables according to your application When doing so observe Chapter 4 5 Connection diagram 4 3 1 Cable routing Water must be prevented from reaching the cable exit along the cable NOT...

Page 8: ...Y Star connection 2 red 5 V L1 black 3 white output L2 blue 4 black 0 V L3 brown 5 4 K7 TOP 2x gray PE green yellow Y Star connection L1 black L2 blue L3 brown Item no 10425 5 9970 ENU Change 236565 A...

Page 9: ...connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WARNING Live terminals and conn...

Page 10: ...e device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmental management system which is certified in acco...

Page 11: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 10425 5 9970 ENU Change 236565 Approved 2021 07 16 Page 11 11 ebm papst Mulfinge...

Reviews: