Operating instructions

W1G200-EA91-45

Translation of the original operating instructions

4.5 Checking connections

;

Ensure isolation from supply (all phases).

;

Make sure a restart is impossible

;

Check the cables for proper fit.

4.6 Switching on the device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Risk of fire
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Before switching on, check the device for visible external damage
and make sure the protective devices are functional.

;

Check the fan's air flow paths for foreign matter and remove any
foreign matter found.

;

Apply the nominal supply voltage.

;

Start the device by changing the input signal.

4.7 Switching off the device

;

Disconnect the device from the power supply at the supply line's
main switch.

5. INTEGRATED PROTECTIVE FEATURES

The integrated protective functions cause the motor to switch off
automatically in the event of the faults described in the table.

Fault

Safety feature description/
function

Rotor position detection error

An automatic restart follows.

Blocked rotor

;

After the blockage is

removed, the motor restarts
automatically.

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ After working on the device, remove any tools or other

objects from the device.

If the device is out of use for some time, e.g. when in storage,
we recommend switching it on for at least two hours to allow
any condensation to evaporate and to move the bearings.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power
supply, apply control
signal.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Page 8 / 10              Revision  0

Summary of Contents for W1G200-EA91-45

Page 1: ...sed by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installat...

Page 2: ...e working on rotating parts Protect long hair with a cap 1 8 Emissions WARNING Depending on the installation and operating conditions the sound pressure level may exceed 70 dB A Risk of noise induced...

Page 3: ...EA91 45 Translation of the original operating instructions Operation with completely or partially disassembled or manipulated protective devices In addition all applications not listed among the inten...

Page 4: ...tructions W1G200 EA91 45 Translation of the original operating instructions 3 TECHNICAL DATA 3 1 Product drawing All dimensions in mm 1 Direction of air flow V 2 Cable AWG20 3x crimped splices Page 4...

Page 5: ...election max min Soft start Thermal overload protection for motor with cable Lateral Protection class II Conformity with standards EN 60335 1 EN 60335 1 EN 60335 2 24 EN 60335 2 80 EN 60335 2 89 CE Ap...

Page 6: ...nvironment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the data on the nameplate match the connection data Befor...

Page 7: ...Operating instructions W1G200 EA91 45 Translation of the original operating instructions 4 4 Connection diagram Drawing preliminary Page 7 10 Revision 0...

Page 8: ...ection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically 6 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repair...

Page 9: ...nd rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following s...

Page 10: ...EA91 45 Translation of the original operating instructions Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on di...

Reviews: