ebm-papst S6E630-AN01-01 Operating Instructions Manual Download Page 8

Operating instructions

S6E630-AN01-01

Translation of the original operating instructions

Fig. 2: Fan installed lying flat, cable routed as a water trap.

Fans installed in upright position

When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 3: Cable routing for fans installed upright.

4.3.4 Motor protection

CAUTION
Voltage

The device is a built-in component with no isolating switch.
→ Connect the device to a suitable tripping device.
→ Only connect the device to circuits which can be de-

energised with an all-pole disconnection switch.

→ When working on the device, the system/machine in

which the device is installed must be secured so as to
prevent it from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect up the thermal overload protector installed in the coil.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect up the thermal overload protector correctly will
invalidate your warranty claim.

U

I

AC

250 V

2.3 A

Item no. 10555-5-9970 · ENG · Revision 230069 · Release 2021-04-15 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S6E630-AN01-01

Page 1: ... specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy...

Page 2: ...the fan there must be sufficient space for people to pass by the fan 1 6 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and sim...

Page 3: ...s Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation O...

Page 4: ... the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10555 5 9970 ENG Revision 230069 Release 2021 04 15 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... Material of blades Press fitted sheet steel blank sprayed with PP plastic Material of guard grille Steel coated in black plastic RAL9005 Number of blades 5 Direction of air flow V Direction of rotation Counter clockwise seen on rotor Type of protection IP54 Insulation class F Humidity F environmental protection class H H2 Mounting position Shaft horizontal or rotor on bottom rotor on top on reque...

Page 6: ... the terminal box is not permitted NOTE Motor capacitor The product is equipped with a motor capacitor with safety protection class P0 S0 according to EN 60252 1 Take this into consideration when fitting it to the end product on the basis of applicable regulations CAUTION Possibility of damage to the device Serious damage may result if the device slips during assembly Keep the device fixed in posi...

Page 7: ...lowing installation in the end device 4 2 4 Frequency inverter Please use a frequency converter only after consultation with ebm papst For operation with frequency converters fit sinusoidal filters that work on all poles phase phase and phase earth between the frequency converter and the motor During operation with frequency converters an all pole sine filter protects the motor against high voltag...

Page 8: ...hen working on the device the system machine in which the device is installed must be secured so as to prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil The motors are equipped with thermal overload protectors to protect the devices Check to make sure...

Page 9: ...s 4 4 Connection screen L U1 blue Z brown N U2 black PE green yellow TOP grey Item no 10555 5 9970 ENG Revision 230069 Release 2021 04 15 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 10: ...ibrations can result from improper handling imbalance resulting from damage during transport or component induced or structural resonances When putting the fan into service determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation a...

Page 11: ...ater jet or high pressure cleaner Do not use any acid alkali or solvent basedcleaning agents Do not use any pointed or sharp edged objects for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rotating parts are not permissible Operate the fan for 2 hours at ...

Page 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 5 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...

Reviews: