3.2 Nominal data

Motor

M6E074-EI

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

ml

ml

Valid for approval/
standard

CE

CE

Speed / min

-1

750

700

Power consumption / W

125

150

Current draw / A

0.56

0.66

Capacitor / µF

3

3

Capacitor voltage / VDB

400

400

Capacitor standard

P0 (CE)

P0 (CE)

Max. back pressure / Pa

40

38

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

70

50

Starting current / A

0.68

0.68

Max. safe operating
speed / min

-1

1500
@ 70 °C

1500
@ 70 °C

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

6.1 kg

Fan size

450 mm

Rotor surface

Painted black

Terminal box material

PC/ABS plastic

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

"V"

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

F1-2

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Electrical hookup

Via terminal box, capacitor integrated and
connected

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Motor capacitor
according to EN 60252-
1 in safety protection
class

P0/S0

Conformity with
standards

EN 60335-1; CE

Approval

EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product drawing.

3.5 Transport and storage conditions

;

Use the device in accordance with its degree of protection.

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 14569-5-9970 · ENU · Change 85321 · Approved 2015-12-09 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S6E450-AM13-50

Page 1: ...operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perfo...

Page 2: ...device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come...

Page 3: ...the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposi...

Page 4: ...sions in mm 1 Direction of air flow V 2 Tightening torque 0 5 0 1 Nm 3 Cable diameter max 7 5 mm tightening torque 1 3 0 2 Nm Item no 14569 5 9970 ENU Change 85321 Approved 2015 12 09 Page 4 10 ebm pa...

Page 5: ...osition Shaft horizontal or rotor on bottom rotor on top on request Condensation drainage holes On rotor side Mode S1 Motor bearing Ball bearing Touch current according to IEC 60990 measuring circuit...

Page 6: ...on data and the data for the operating capacitor Before connecting the device make sure the power supply matches the device voltage Only use cables designed for the current level indicated on the name...

Page 7: ...e terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable Fans installed lying flat Make sure the cable is routed in a U shaped loop Fig 2 Fan installed...

Page 8: ...instructions 4 4 Connection diagram PE green yellow L black N blue Item no 14569 5 9970 ENU Change 85321 Approved 2015 12 09 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phon...

Page 9: ...nnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WARNING Live t...

Page 10: ...s and housing Visual inspection At least every 6 months Replacement of device Fastening the cables Visual inspection At least every 6 months Fasten Fastening the protective earth terminal Visual inspe...

Reviews: