background image

Operating instructions

S4D450-GA14-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D094-HA

Phase

3~

3~

3~

3~

Nominal voltage / VAC

400

400

400

400

Connection

Δ

Y

Δ

Y

Frequency / Hz

50

50

60

60

Type of data definition

fa

fa

fa

fa

Valid for approval /
standard

CE

CE

CE

CE

Speed / min

-1

1410

1220

1610

1200

Power input / W

355

270

535

360

Current draw / A

0.85

0.47

1.17

0.63

Max. back pressure / Pa

200

110

110

55

Min. ambient temperature
/ °C

-40

-40

-40

-40

Max. ambient
temperature
/ °C

70

70

50

50

Starting current / A

3.9

1.3

3.5

1.2

Maximum safe operating
speed / min

-1

1800

1800

1800

1800

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

39.4

27.3

31.3

Efficiency grade N

48.1

36

40

Power input P

e

/ kW

0.42

Air flow q

v

/ m³/h

4500

Pressure increase total p

sf

/ Pa

135

Speed n / min

-1

1385

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

10 kg

Size

450 mm

Surface of rotor

Coated in black

Material of terminal box

ABS plastic, black

Material of blades

Sheet steel, coated in black

Material of guard grille

Steel, phosphated and coated in black
plastic

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F3-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60034-1 (2004); CE

Approval

CCC; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 10876-5-9970 · Revision 82546 · Release 2014-05-08 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S4D450-GA14-01

Page 1: ... specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without ...

Page 2: ...that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on r...

Page 3: ...sing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that ...

Page 4: ...ve the unit mm 1 Direction of air flow V 2 Tightening torque 1 0 0 15 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 15 Nm Item no 10876 5 9970 Revision 82546 Release 2014 05 08 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...al of blades Sheet steel coated in black Material of guard grille Steel phosphated and coated in black plastic Number of blades 5 Direction of air flow V Direction of rotation Counter clockwise seen on rotor Type of protection IP 54 Insulation class F Humidity class F3 1 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mo...

Page 6: ...ing an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The prot...

Page 7: ...e ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection CAUTION Voltage The device is a built in component with no isolating switch Connect the device to a suitable tripping device Only connect the device to circuits which can be de energised with an all pole disconnection swi...

Page 8: ...nection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 10876 5 9970 Revision 82546 Release 2014 05 08 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ... that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use including the required safety mechanisms and professional electrical connection This also applies for devices which have already been equipped with plugs and terminals or similar connectors by the customer...

Page 10: ...ion diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overtemperature of motor Ambient temperature too high Lower ambient temperature if possible Insufficient cooling Improve cooling If you have any other problems contact ebm papst 5 1 Cleaning NOTE Damage to...

Reviews: