background image

Operating instructions

S4D450-AP03-10

Translation of the original operating instructions

2. PROPER USE

The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.

Proper use also includes:

Use the device in power systems with earthed neutral (TN/TT power
systems) only.

Moving air with a density of 1.2 kg/m³.

Using the device in accordance with the permitted ambient
temperature, see chapter 3.5 Transport and storage conditions and
chapter 3.2 Nominal data.

Operating the device with all protective features in place.

Minding the operating instructions.

Improper use

Using the device in the following ways is particularly prohibited and
may cause hazards:

Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.

Opening the terminal box during operation.

Moving air that contains abrasive particles.

Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.

Moving air that contains dust pollution, e.g. suctioning off saw dust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or for taking on safety-
related functions.

Operation with completely or partially disassembled or modified
protective features.

In addition, all application options that are not listed under proper use.

Item no. 13846-5-9970 · ENG · Revision 84662 · Release 2015-03-02 · Page 3 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for S4D450-AP03-10

Page 1: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Page 2: ... install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm papst 1 4...

Page 3: ...g on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 8 Emission WARNING Depending on the installation and operating conditions...

Page 4: ...ns Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly...

Page 5: ...ightening torque 0 5 0 1 Nm 3 Cable diameter max 10 mm tightening torque 1 3 0 2 Nm Item no 13846 5 9970 ENG Revision 84662 Release 2015 03 02 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 6: ... side Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Electrical leads Via terminal box Cable exit Variable Protection class I if protective earth is connected by customer Product conforming to standard EN 60335 1 motor does not have factory installed overheating protection For cyclic speed loads note that the rotating parts of the...

Page 7: ... connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables ...

Page 8: ...ed in the form of a loop water trap Fig 2 Fan installed lying flat cable routed as a water trap Fans installed in upright position When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection WARNING Device without overheating protection The device is delivered...

Page 9: ...k L2 blue L3 brown PE green yellow Item no 13846 5 9970 ENG Revision 84662 Release 2015 03 02 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 10: ...erly tightened 4 7 Switch on device The device is not to be switched on until it has been installed properly and in accordance with its intended use including the required protective devices and professional electrical connection This also applies to devices which have already been equipped with plugs and terminals or similar connectors by the customer WARNING Hot motor housing Fire hazard Ensure ...

Page 11: ...oint Overtemperature of motor Ambient temperature too high Lower ambient temperature if possible Insufficient cooling Improve cooling If you have any other problems contact ebm papst 5 1 Cleaning NOTE Damage to the device during cleaning Malfunction possible Do not clean the device using a water jet or high pressure washer Do not use any cleaners containing acids bases or solvents Do not use any p...

Page 12: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Reviews: