ebm-papst S4D315-BP10-31 Operating Instructions Manual Download Page 7

Operating instructions

S4D315-BP10-31

Translation of the original operating instructions

4.4 Connection screen

Note: Direction of rotation changes when two phases are reversed

Δ

Delta connection

Y

Star connection

L1

black

L2

blue

L3

brown

U1

black

V1

blue

W1

brown

U2

green

V2

white

W2

yellow

Item no. 10663-5-9970 · Revision 75331 · Release 2011-11-23 · Page 7 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S4D315-BP10-31

Page 1: ...the electrical system Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modific...

Page 2: ... could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect...

Page 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Page 4: ... drawing All measures have the unit mm 1 Connection line PVC 7x brass lead tips crimped 2 Direction of air flow A Item no 10663 5 9970 Revision 75331 Release 2011 11 23 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...r on top on request Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Cable exit Axial Protection class I if protective earth is connected by customer Product conforming to standard EN 60335 1 motor does not have factory installed overheating protection For cyclic speed loads note that the rotati...

Page 6: ...switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross...

Page 7: ...en two phases are reversed Δ Delta connection Y Star connection L1 black L2 blue L3 brown U1 black V1 blue W1 brown U2 green V2 white W2 yellow Item no 10663 5 9970 Revision 75331 Release 2011 11 23 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury Keep out of the danger zone of the device When working on the device switch off the mains supply voltage and secure the latter from being switched on again Wait until the device stops If the device remains out of use for some time e g when in storage we recommend switching the device on for at...

Page 9: ...acement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore hole...