Operating instructions

S4D300-AS34-37

Translation of the original operating instructions

2. PROPER USE

The device is exclusively designed as a built-in device for moving air
according to its technical data.
Any other or secondary use is deemed improper and constitutes a
misuse of the device.
Installations on the customer's side must meet the mechanical, thermal
and service life-related stresses that can occur.

Proper use also includes:

Use the device in power systems with earthed neutral (TN/TT power
systems) only.

Moving air with a density of 1.2 kg/m³.

Using the device in accordance with the permitted ambient
temperature, see chapter 3.5 Transport and storage conditions and
chapter 3.2 Nominal data.

Operating the device with all protective features in place.

Minding the operating instructions.

Improper use

Using the device in the following ways is particularly prohibited and
may cause hazards:

Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.

Opening the terminal box during operation.

Moving air that contains abrasive particles.

Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.

Moving air that contains dust pollution, e.g. suctioning off saw dust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or for taking on safety-
related functions.

Operation with completely or partially disassembled or modified
protective features.

In addition, all application options that are not listed under proper use.

Item no. 12198-5-9970 · Revision 76115 · Release 2012-02-23 · Page 3 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S4D300-AS34-37

Page 1: ...ised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions o...

Page 2: ...ulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with app...

Page 3: ...sing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that ...

Page 4: ...ave the unit mm 1 Direction of air flow A 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 12198 5 9970 Revision 76115 Release 2012 02 23 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... blades 5 Direction of air flow A Direction of rotation Clockwise seen on rotor Type of protection IP 44 Depending on installation and position as per EN 60034 5 Insulation class B Humidity class F2 2 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring ...

Page 6: ...ust have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG26 0 13 mm Earth wire contact resistance in accordance with EN 60335 Compliance with the impedance specifications in accordance with EN 60335 for the protective earth circuit must be verified in the end application Depen...

Page 7: ...crewed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection WARNING Device without overheating protection The device is delivered without any automatically functioning overheating protection The device can become hot and burn For the version without TOP install an additional suitable motor protectio...

Page 8: ...g two phases Three phase motor Δ Delta connection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown U2 green V2 white W2 yellow PE green yellow Item no 12198 5 9970 Revision 76115 Release 2012 02 23 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ... that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use including the required safety mechanisms and professional electrical connection This also applies for devices which have already been equipped with plugs and terminals or similar connectors by the customer...

Page 10: ...m Unacceptable operating point Check operating point Overtemperature of motor Ambient temperature too high Lower ambient temperature if possible Insufficient cooling Improve cooling If you have any other problems contact ebm papst 5 1 Cleaning NOTE Damage to the device during cleaning Malfunction possible Do not clean the device using a water jet or high pressure washer Do not use any cleaners con...

Reviews: