ebm-papst S3G910-BO84-21 Operating Instructions Manual Download Page 9

Operating instructions

S3G910-BO84-21

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1,2

PE

green/
yellow

Protective earth

1

3

N

blue

Power supply, neutral conductor, 50/60 Hz

1

4

L

black

Power supply, phase, 50/60 Hz

1

5

COM

white 1

Floating status contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)

1

6

NC

white 2

Floating status contact, break for failure

2

8

0-10 V

yellow

Control input, set value 0-10 VDC, impedance 100 kΩ, SELV

2

11

10 VDC

red

Voltage output 10 VDC (±3%), max. 10 mA, power supply for external devices (e.g.
potentiometer), SELV

2

12

GND

blue

Reference ground for control interface, SELV

Item no. 50604-5-9970 · ENU · Change 205336 · Approved 2020-07-16 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S3G910-BO84-21

Page 1: ...d specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the...

Page 2: ... g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body par...

Page 3: ... device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ic...

Page 4: ... dimensions in mm 1 Direction of air flow V 2 Cable PVC AWG18 6x crimped ferrules 3 Cable PVC AWG22 3x crimped ferrules Item no 50604 5 9970 ENU Change 205336 Approved 2020 07 16 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...s determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 19 7 kg Size 910 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted sheet steel blank sprayed with PP plastic Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Airflow...

Page 6: ...fety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to remove the device from its packaging CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface Make sure the blades are not subjected to load Following installation make sure the impeller moves easily and that the blades of the...

Page 7: ...active currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typica...

Page 8: ...ory settings made for the device by ebm papst Mode PWM control Group address 01 Fan device address 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value requirement Analog Direction of action Positive heating Item no 50604 5 9970 ENU Change 205336 Approved 2020 07 16 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de e...

Page 9: ...eak for failure 2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kΩ SELV 2 11 10 VDC red Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometer SELV 2 12 GND blue Reference ground for control interface SELV Item no 50604 5 9970 ENU Change 205336 Approved 2020 07 16 ...

Page 10: ...round connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety feature description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outsi...

Page 11: ...ny cleaning agents used If severe corrosion is visible on load bearing or rotating parts switch off the device immediately and replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate vibrations the fan may need to be rebalanced To have it rebalanced contact eb...

Page 12: ...ents could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are mostly made of steel copper aluminum and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...