ebm-papst S3G500-AM56-21 Operating Instructions Manual Download Page 5

Operating instructions

S3G500-AM56-21

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-EA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed / min

-1

1420

Power consumption / W

750

Current draw / A

3.4

Max. back pressure / Pa

175

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to ErP Directive

Actual

Req. 2015

01 Overall efficiency η

es

/ %

41.6

32.8

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

48.8

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

S3G500-AM56-21

09 Power consumption P

ed

/ kW

0.73

09 Air flow q

v

/ m³/h

5850

09 Pressure increase total p

sf

/

Pa

173

10 Speed n / min

-1

1425

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

11 kg

Fan size

500 mm

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

"V"

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

F4-1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Alarm relay
- Motor current limitation
- PFC, active
- Soft start
- Control input 0-10 VDC
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

CCC; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

Item no. 50317-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

[email protected]  

Summary of Contents for S3G500-AM56-21

Page 1: ...ied trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product Note the following when working on the device Do not perf...

Page 2: ...or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can be...

Page 3: ...g the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sustaining or life support function Operation with external vibrations Conveying solids in the flow medium Painting the device Connections e g screws coming loose during operation Conveying air that ...

Page 4: ... in mm 1 Direction of air flow V 2 Cable PVC AWG 18 5x crimped ferrules 3 Cable PVC AWG 22 3x crimped ferrules Item no 50317 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com zakaz ventilatorry ru ...

Page 5: ...P data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 11 kg Fan size 500 mm Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted sheet steel blank sprayed with PP plastic Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Airflow dire...

Page 6: ...device in accordance with your application CAUTION Possible damage to the device If the device slips during installation serious damage can result Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the protective ...

Page 7: ...can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on The values are typically less than 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current circuit breaker RCCB Only universal residual current devices type B or B are allowed As with variable frequency drives residu...

Page 8: ...up address 1 Fan device address 1 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value requirement Analog Direction of action Positive heating Item no 50317 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com zakaz ventilatorry ru ...

Page 9: ...ilure 2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kΩ SELV 2 11 10 VDC red Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometer SELV 2 12 GND blue Reference ground for control interface SELV Item no 50317 5 9970 ENU Change 89187 Approved 2016 04 15 Page 9 12 e...

Page 10: ...on error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line voltage returns to permitted values the motor restarts automatically 6 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for...

Page 11: ... an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 6 3 1 Country specific le...

Page 12: ...lectronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50317 5 9970 ENU Change 89187 Approved 2016 04 15 Page 12 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com zakaz ventilatorry ru ...