ebm-papst S3G350-AN01-52 Operating Instructions Manual Download Page 5

Operating instructions

S3G350-AN01-52

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-CF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

1475

Power input / W

165

Current draw / A

1.35

Max. back pressure / Pa

100

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Actual

Request 2015

01 Overall efficiency η

es

/ %

39.8

28.6

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

51.2

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

S3G350-AN01-52

09 Power input P

ed

/ kW

0.16

09 Air flow q

v

/ m³/h

2400

09 Pressure increase total p

sf

/

Pa

87

10 Speed n / min

-1

1495

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

3.7 kg

Size

350 mm

Material of terminal box

ABS plastic

Material of blades

Press-fitted sheet steel blank, sprayed
with PP plastic

Material of guard grille

Steel, coated in black plastic (RAL9005)

Number of blades

5

Direction of air flow

"V"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Humidity (F)/
environmental
protection class (H)

F3-1

Mounting position

Any

Condensate discharge
holes

None, open rotor

Cooling bore / aperture

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 1.1 mA
- Tach output
- Output limit
- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

PTC resistor

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1; CE

Approval

CCC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

You can obtain additional mounting data from the product drawing if
necessary.

Item no. 51542-5-9970 · ENG · Revision 85000 · Release 2015-04-29 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S3G350-AN01-52

Page 1: ...s are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approva...

Page 2: ...egrating the device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair danglin...

Page 3: ...e operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and...

Page 4: ...s have the unit mm 1 Direction of air flow V 2 Tightening torque 0 5 0 1 Nm 3 Cable diameter 7 5 mm tightening torque 1 3 0 2 Nm Item no 51542 5 9970 ENG Revision 85000 Release 2015 04 29 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 3 7 kg Size 350 mm Material of terminal box ABS plastic Material of blades Press fitted sheet steel blank sprayed with PP plastic Material of guard grille Steel coated in black plastic RAL9005 Number of blades 5 Direction of air flow V Direction of rotation Counter clockwise seen on rotor Type of pr...

Page 6: ... customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device...

Page 7: ...move the cap only in those places where cables are inserted Insert the line s not included in the standard scope of delivery into the terminal box First connect the PE protective earth connection Connect the lines to the corresponding terminals Use a screwdriver to do so During the connection work ensure that no cables splice off Seal the terminal box 4 3 3 Cable routing No water may penetrate alo...

Page 8: ... GND Connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10V max 1 1mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof Isink 10 mA 4 Tach white Tach output open collector 1 pulse per revolution electrically isolated Isink max 10 mA Item no 51542 5 9970 ENG Revision 85000 Release 2015 04 29 Page 8 11 ebm papst Mulfinge...

Page 9: ...devices which have already been equipped with plugs and terminals or similar connectors by the customer WARNING Hot motor housing Fire hazard Ensure that no combustible or flammable materials are located close to the fan Inspect the device for visible external damage and the proper function of the protective features before switching it on Check the air flow paths of the fan for foreign objects an...

Page 10: ... 25 s and switch it on again Ambient temperature too high Reduce the ambient temperature Reset by reducing control input to 0 Unacceptable operating point Correct the operating point Let the device cool down If you have any other problems contact ebm papst 6 1 Cleaning NOTE Damage to the device during cleaning Malfunction possible Do not clean the device using a water jet or high pressure cleaner ...

Page 11: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...