background image

Operating instructions

S3G250-AD54-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-CF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

me

Speed / min

-1

3050

Power input / W

170

Current draw / A

1.25

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

43.3

24.8

28.8

Efficiency grade N

54.5

36

40

Power input P

ed

/ kW

0.17

Air flow q

v

/ m³/h

1355

Pressure increase total p

sf

/ Pa

176

Speed n / min

-1

2875

Data established at point of optimum efficiency

3.4 Technical features

Mass

2.92 kg

Size

250 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of blades

Sheet steel, coated in black

Material of guard grille

Steel, phosphated and coated in black
plastic

Number of blades

9

Direction of air flow

"A"

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 44

Insulation class

"B"

Humidity class

F3-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Control input 0-10 VDC / PWM
- Output 10 VDC, max. 1.1 mA
- Tach output
- Over-temperature protected
electronics / motor
- Motor current limit
- Soft start

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CCC; CSA C22.2 Nr.77; UL 2111

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.7 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-3

Item no. 50175-5-9970 · Revision 73571 · Release 2011-02-18 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for S3G250-AD54-01

Page 1: ...rsonnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the appro...

Page 2: ...tire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the devi...

Page 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Page 4: ...e unit mm 1 Direction of air flow A 2 Connecting line AWG18 3 x crimped core end sleeves 3 Connecting line AWG22 4 x crimped core end sleeves Item no 50175 5 9970 Revision 73571 Release 2011 02 18 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...nsate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Control input 0 10 VDC PWM Output 10 VDC max 1 1 mA Tach output Over temperature protected electronics motor Motor current limit Soft start Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protectio...

Page 6: ... are possible Maintain a distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recommendation clearance 10 cm separate cable routing NOTE Water penetration into leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device o...

Page 7: ...h 8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V max 1 1 mA electrically isolated 12 GND blue GND Connection for control interface Item no 50175 5 9970 Revision 73571 Release 2011 02 18 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mul...

Page 8: ...he device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Discon...

Page 9: ...otector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Ambient temperature too high Reduce the ambient temperature Reset by reducing contro...

Page 10: ...6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut off state At least every 6 months Replace device in case of noise difficulty of movement or clearance of the bearings Item no 50175 5 9970 Revision 73571 Relea...

Page 11: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information ebm papst S3G250 AD54 01 ...