background image

Operating instructions

S1G300-CA19-02

Translation of the original operating instructions

4.5 Checking connections

;

Ensure isolation from supply (all phases).

;

Make sure a restart is impossible

;

Check the cables for proper fit.

4.6 Switching on the device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Risk of fire
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Before switching on, check the device for visible external damage
and make sure the protective devices are functional.

;

Check the fan's air flow paths for foreign matter and remove any
foreign matter found.

;

Apply the nominal supply voltage.

;

Start the device by changing the input signal.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ Low-vibration operation of the fan must be ensured over the

entire speed control range.

→ Severe vibration can arise for instance from inexpert

handling, transportation damage and resultant imbalance or
be caused by component or structural resonance.

→ Speed ranges with excessively high vibration levels and

possibly resonant frequencies must be determined in the
course of fan commissioning.

→ Either run through the resonant range as quickly as

possible with speed control or find another remedy.

→ Operation with excessively high vibration levels can

lead to premature failure.

4.7 Switching off the device

;

Disconnect the device from the power supply at the supply line's
main switch.

5. INTEGRATED PROTECTIVE FEATURES

The integrated protective functions cause the motor to switch off
automatically in the event of the faults described in the table.

Fault

Safety feature description/
function

Rotor position detection error

An automatic restart follows.

Blocked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Motor overload

After cooling off, the device
restarts automatically.

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

NOTE

If the device is not operated for a lengthy period in installed
condition in a dry environment, it is to be started up and
operated at full speed for one hour at least every four months. If
the device is not operated for a lengthy period in installed
condition in a damp environment (e.g. outdoors), it is to be
started up and operated at full speed for at least two hours once
a month to move the bearings and allow any condensate that
may have ingressed to evaporate.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Item no. 50091-5-9970 · ENU · Change 205631 · Approved 2019-07-26 · Page 9 / 11

·

·

·

·

·

·

Summary of Contents for S1G300-CA19-02

Page 1: ...and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be...

Page 2: ...tic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long ha...

Page 3: ...g the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation of the device in the camping area or similar applications Operation in medical equipment with a li...

Page 4: ...2 Translation of the original operating instructions 3 TECHNICAL DATA 3 1 Product drawing All dimensions in mm 1 Direction of air flow A 2 Cable AWG20 3x crimped splices Item no 50091 5 9970 ENU Change 205631 Approved 2019 07 26 Page 4 11 ...

Page 5: ...ice are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may change during the production period This has no effect on strength dimensional stab...

Page 6: ...an is installed so as to prevent it from being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the namepla...

Page 7: ...nstructions Fig 2 Cable routing for fans installed upright The cables must always be routed downward NOTE Cable routing is to be performed accordingly if use is made of the ESM plug in module to connect the fan Item no 50091 5 9970 ENU Change 205631 Approved 2019 07 26 Page 7 11 ...

Page 8: ...Operating instructions S1G300 CA19 02 Translation of the original operating instructions 4 4 Connection diagram Drawing preliminary Item no 50091 5 9970 ENU Change 205631 Approved 2019 07 26 Page 8 11 ...

Page 9: ...rated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety feature description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Motor overload After cooling off the device restarts automatically 6 MAINTENANCE MALFUNCTIONS POSSIB...

Page 10: ...off the device immediately and replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate vibrations the fan may need to be rebalanced To have it rebalanced contact ebm papst The fan is equipped with maintenance free ball bearings The lifetime lubrication of the ...

Page 11: ...Component disposal The products are mostly made of steel copper aluminum and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires...