6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor will restart automatically, e.g. after a mains
failure.

Risk of injury
→ Keep out of the device hazard zone.
→ When working on the device, switch off the mains power

and ensure that it cannot be switched back on.

→ Wait until the device stops.
→ After working on the device, remove any tools used or

other objects from the device.

NOTE

If the device is not operated for a lengthy period in installed
condition in a dry environment, it is to be started up and
operated at full speed for one hour at least every four months. If
the device is not operated for a lengthy period in installed
condition in a damp environment (e.g. outdoors), it is to be
started up and operated at full speed for at least three hours
once a month to move the bearings and allow any condensate
that may have ingressed to evaporate.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after cleaning,
replace the device.
If you have
attached any weight
clips during cleaning,
make sure to remove
them afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains supply
voltage,
restore power
supply.
Important! The error
message resets
automatically.
The device starts up
again automatically
without advance
warning.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Motor winding broken Replace device
Insufficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Ambient temperature
too high

Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Unacceptable
operating point (e.g.
counterpressure is
too high)

Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

If you have any other problems, contact ebm-papst.

6.1 Vibration test

Checking the fan for mechanical vibrations based on ISO 14694.
Recommendation: every 6 months. Maximum vibration severity is 3.5
mm/s measured at the motor’s fastening diameter on the motor support
plate towards and perpendicular to the motor’s axis of rotation.

Item no. 52489-5-9970 · ENG · Revision 209539 · Release 2021-02-01 · Page 13 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G710-AP02-01

Page 1: ...rry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidiness in the working area increases the risk of ...

Page 2: ...until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk of injury Do not wear any loose fitting...

Page 3: ...ing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in fl...

Page 4: ... 2 4013 with pressure tap not included in scope of delivery 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 52489 5 9970 ENG Revision 209539 Release 2021 02 01 Page 4 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 44 kg Size 710 mm Motor size 150 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Material of impeller Aluminium sheet Number of blades 7 Direction of rotation Clockwise seen on rotor Type of protection IP5...

Page 6: ...device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND START UP 4 1 Connecting the mechanical system CAUTION Cutting and crushing hazard when removing the fan from the packaging Carefully hold the impeller to remove the device from its packaging Make sure to avoid any shock Wear safety shoes an...

Page 7: ...nment of conductor cross sections and the fuse protection required for them overload protection only no device protection Nominal voltage Safety fuse Automatic circuit breaker Wire cross section Wire cross section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 AWG American Wire Gauge 4 2 3 Idle current...

Page 8: ...a screwdriver to do so During the connection work ensure that no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the consta...

Page 9: ...g Control mode parameter set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function parameter set 2 Positive heating Item no 52489 5 9970 ENG Revision 209539 Release 2021 02 01 Page 9 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938...

Page 10: ...contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS 485 RSA MODBUS RTU SELV KL 3 2 RSB Bus connection RS 485 RSB MODBUS RTU SELV KL 3 3 10 GND Signal ground for control interface SELV KL 3 4 Ain1 U Analogue input 1 set value 0 10 V Ri 100 kΩ parametrisable curve only usable as alternativ...

Page 11: ...OM setting the controller function of the integrated controller is normally inversely selectable per bus or per digital input Din 3 normal open pin or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC SELV KL 3 11 Ain2 U Analogue input 2 actual value 0 10 V Ri 100 kΩ parametrisable curve only usable as alternative to input Ain2 SELV KL 3 12 20 V Fixed voltage output 20 VDC 20...

Page 12: ...ance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature failure The maximum vibration severity may not exceed 3 5 mm s and should be checked every 6 months It must be measured at least in and perpendicular to the axial direction at the place where the mot...

Page 13: ...ff de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the device cool...

Page 14: ... this period Adapt the maintenance intervals to the dust pollution occurring 6 3 Safety test NOTE High voltage test The integrated EMC filter contains Y capacitors Therefore the trigger current is exceeded when AC testing voltage is applied Test the device with DC voltage when you carry out the high voltage test required by law The voltage to be used corresponds to the peak value of the AC voltage...

Page 15: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminium Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets ...