ebm-papst R3G630-RA38-21 Operating Instructions Manual Download Page 9

Operating instructions

R3G630-RA38-21

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

KL1

1

L1

Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz

KL1

2

N

Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz

PE

PE

Earth connection, PE connection

KL2

1

NO

Status relay, floating status contact; option 1: close with error; option 2: close with run monitor error message

KL2

2

COM

Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact; option 1: break with error; option 2: break with error for run monitor error
message

KL3

1

RSA

Bus connection RS485; RSA; MODBUS RTU

KL3

2

RSB

Bus connection RS485; RSB; MODBUS RTU

KL3

3

GND

Signal ground for control interface

KL3

4

Ain1 U

Analog input 1 (set value); 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to input
Ain1 I

KL3

5

+10 V

Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext. devices
(e.g. potentiometer)

KL3

6

Ain1 I

Analog input 1 (set value); 4-20 mA; Ri= 100 Ohm; parametrisable curve; only usable as alternative to input
Ain1 U

KL3

7

Din1

Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridge to
GND or applied voltage < 0.8 VDC; reset function: triggers software reset after a level change to <0.8 V

KL3

8

Din2

Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set is
selectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC;
parameter set 2: bridge to GND or applied voltage < 0.8 VDC

KL3

9

Din3

Digital input 3: control characteristic of the integrated controller; according to EEPROM setting, the control
characteristic of the integrated controller is normally/inversely selectable per BUS or per digital input; normal:
open pin or applied voltage 5 to 50 VDC; inverse: bridge to GND or applied voltage < 0.8 VDC

KL3

10

GND

Signal ground for control interface

KL3

11

Ain2 U

Analog input 2; actual sensor value 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to
input Ain2 I

KL3

12

+20 V

Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; power supply for ext.
devices (e.g. sensors)

KL3

13

Ain2 I

Analog input 2; actual sensor value 4-20 mA; Ri= 100 Ohm; parametrisable curve; only alternative to input
Ain2 U

KL3

14

Aout

Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/ of
the actual motor speed. Parametrisable curve.

Item no. 51874-5-9970 · Revision 82539 · Release 2014-05-08 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G630-RA38-21

Page 1: ...o install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re e...

Page 2: ...g on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing...

Page 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Page 4: ...3300 2 4013 not included in the standard scope of delivery 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 51874 5 9970...

Page 5: ...g Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Tach output Input for sensor 0 10 V or 4 20 mA External 24 V input programming External releas...

Page 6: ...her the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for curre...

Page 7: ...es where cables are inserted Mount the screwed cable glands with the seal inserts provided in the terminal box Insert the line s not included in the standard scope of delivery into the terminal box Fi...

Page 8: ...ter set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function pa...

Page 9: ...DC disabling bridge to GND or applied voltage 0 8 VDC reset function triggers software reset after a level change to 0 8 V KL3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setti...

Page 10: ...f the protective features before switching it on Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device...

Page 11: ...gise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Page 12: ...every 6 months Clean or replace impeller Tightness of screwed cable gland Visual inspection At least every 6 months Retighten replace if damaged Condensate discharge holes for clogging as necessary V...